🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.63%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.88V (0.78%)
Voltage at Load End238.5 VLoss: 1.52 V (1116.2 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A277.01 V (115.42%)0.0 V456.94 V (190.39%)203913.4 WDrop/Amp High
12 AWG3.31 mm²20 A174.07 V (72.53%)65.9 V287.14 V (119.64%)128138.9 WDrop/Amp High
10 AWG5.26 mm²30 A109.54 V (45.64%)130.5 V180.69 V (75.29%)80635.0 WDrop/Amp High
8 AWG8.37 mm²50 A68.84 V (28.68%)171.2 V113.55 V (47.31%)50673.8 WDrop/Amp High
6 AWG13.3 mm²65 A43.32 V (18.05%)196.7 V71.46 V (29.78%)31890.2 WDrop/Amp High
4 AWG21.15 mm²85 A27.24 V (11.35%)212.8 V44.94 V (18.72%)20053.9 WDrop/Amp High
3 AWG26.67 mm²100 A21.6 V (9.0%)218.4 V35.64 V (14.85%)15903.3 WDrop/Amp High
2 AWG33.62 mm²115 A17.14 V (7.14%)222.9 V28.27 V (11.78%)12615.7 WDrop/Amp High
1 AWG42.41 mm²130 A13.59 V (5.66%)226.4 V22.41 V (9.34%)10000.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.77 V (4.49%)229.2 V17.77 V (7.4%)7929.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.54 V (3.56%)231.5 V14.1 V (5.87%)6290.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.78 V (2.82%)233.2 V11.18 V (4.66%)4989.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.37 V (2.24%)234.6 V8.87 V (3.69%)3956.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.55 V (1.89%)235.5 V7.5 V (3.13%)3347.6 WDrop/Amp High
300 kcmil152.0 mm²285 A3.79 V (1.58%)236.2 V6.25 V (2.61%)2790.4 WDrop/Amp High
350 kcmil177.3 mm²310 A3.25 V (1.35%)236.8 V5.36 V (2.23%)2392.2 WDrop/Amp High
400 kcmil202.7 mm²335 A2.84 V (1.18%)237.2 V4.69 V (1.95%)2092.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.27 V (0.95%)237.7 V3.75 V (1.56%)1673.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.9 V (0.79%)238.1 V3.13 V (1.3%)1395.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.52 V (0.63%)238.5 V2.5 V (1.04%)1116.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A1.14 V (0.47%)238.9 V1.88 V (0.78%)837.1 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 120 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 1.52V (0.63%) and delivers 238.5V at the load.

What size aluminum wire is required for 425 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.88V (0.78%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.