🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

425 Amp Wire Size at 40 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 425 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.63V (0.26%)
Voltage at Load End239.5 VLoss: 0.51 V (372.1 W)
Power & Breaker (125%)176.67 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 425 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A92.34 V (38.47%)147.7 V152.31 V (63.46%)67971.1 WDrop/Amp High
12 AWG3.31 mm²20 A58.02 V (24.18%)182.0 V95.71 V (39.88%)42713.0 WDrop/Amp High
10 AWG5.26 mm²30 A36.51 V (15.21%)203.5 V60.23 V (25.1%)26878.3 WDrop/Amp High
8 AWG8.37 mm²50 A22.95 V (9.56%)217.1 V37.85 V (15.77%)16891.3 WDrop/Amp High
6 AWG13.3 mm²65 A14.44 V (6.02%)225.6 V23.82 V (9.93%)10630.1 WDrop/Amp High
4 AWG21.15 mm²85 A9.08 V (3.78%)230.9 V14.98 V (6.24%)6684.6 WDrop/Amp High
3 AWG26.67 mm²100 A7.2 V (3.0%)232.8 V11.88 V (4.95%)5301.1 WDrop/Amp High
2 AWG33.62 mm²115 A5.71 V (2.38%)234.3 V9.42 V (3.93%)4205.2 WDrop/Amp High
1 AWG42.41 mm²130 A4.53 V (1.89%)235.5 V7.47 V (3.11%)3333.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.59 V (1.5%)236.4 V5.92 V (2.47%)2643.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.85 V (1.19%)237.2 V4.7 V (1.96%)2096.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.26 V (0.94%)237.7 V3.73 V (1.55%)1663.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.79 V (0.75%)238.2 V2.96 V (1.23%)1318.8 WDrop/Amp High
250 kcmil126.7 mm²255 A1.52 V (0.63%)238.5 V2.5 V (1.04%)1115.9 WDrop/Amp High
300 kcmil152.0 mm²285 A1.26 V (0.53%)238.7 V2.08 V (0.87%)930.1 WDrop/Amp High
350 kcmil177.3 mm²310 A1.08 V (0.45%)238.9 V1.79 V (0.74%)797.4 WDrop/Amp High
400 kcmil202.7 mm²335 A0.95 V (0.39%)239.1 V1.56 V (0.65%)697.5 WDrop/Amp High
500 kcmil253.4 mm²380 A0.76 V (0.32%)239.2 V1.25 V (0.52%)557.9 WDrop/Amp High
600 kcmil304.0 mm²420 A0.63 V (0.26%)239.4 V1.04 V (0.43%)465.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.51 V (0.21%)239.5 V0.83 V (0.35%)372.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.38 V (0.16%)239.6 V0.63 V (0.26%)279.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 425 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 425A load over 40 feet one-way at 240V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 0.51V (0.21%) and delivers 239.5V at the load.

What size aluminum wire is required for 425 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.63V (0.26%).

What breaker size is needed for a 425A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (425A × 1.25 = 531.2A), which corresponds to a standard 600A circuit breaker.