475 Amp Wire Size at 250 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)9× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.83%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.04V (42.03%)
Voltage at Load End11.7 VLoss: 0.34 V (161.4 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 250 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A744.78 V (6206.51%)0.0 V1228.54 V (10237.85%)353771.3 WDrop/Amp High
12 AWG3.31 mm²20 A468.02 V (3900.17%)0.0 V772.01 V (6433.45%)222309.5 WDrop/Amp High
10 AWG5.26 mm²30 A294.51 V (2454.29%)0.0 V485.81 V (4048.43%)139894.4 WDrop/Amp High
8 AWG8.37 mm²50 A185.08 V (1542.36%)0.0 V305.3 V (2544.17%)87914.5 WDrop/Amp High
6 AWG13.3 mm²65 A116.48 V (970.64%)0.0 V192.13 V (1601.11%)55326.6 WDrop/Amp High
4 AWG21.15 mm²85 A73.25 V (610.38%)0.0 V120.82 V (1006.84%)34791.7 WDrop/Amp High
3 AWG26.67 mm²100 A58.09 V (484.05%)0.0 V95.81 V (798.45%)27590.7 WDrop/Amp High
2 AWG33.62 mm²115 A46.08 V (383.98%)0.0 V76.01 V (633.39%)21887.1 WDrop/Amp High
1 AWG42.41 mm²130 A36.53 V (304.4%)0.0 V60.25 V (502.12%)17350.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A28.96 V (241.35%)0.0 V47.77 V (398.11%)13756.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.97 V (191.45%)0.0 V37.9 V (315.8%)10912.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.22 V (151.86%)0.0 V30.06 V (250.5%)8656.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.45 V (120.42%)0.0 V23.84 V (198.64%)6864.2 WDrop/Amp High
250 kcmil126.7 mm²255 A12.23 V (101.89%)0.0 V20.17 V (168.07%)5807.8 WDrop/Amp High
300 kcmil152.0 mm²285 A10.19 V (84.93%)1.8 V16.81 V (140.1%)4841.1 WDrop/Amp High
350 kcmil177.3 mm²310 A8.74 V (72.81%)3.3 V14.41 V (120.11%)4150.3 WDrop/Amp High
400 kcmil202.7 mm²335 A7.64 V (63.69%)4.4 V12.61 V (105.06%)3630.2 WDrop/Amp High
500 kcmil253.4 mm²380 A6.11 V (50.95%)5.9 V10.08 V (84.04%)2903.9 WDrop/Amp High
600 kcmil304.0 mm²420 A5.1 V (42.47%)6.9 V8.41 V (70.05%)2420.5 WDrop/Amp High
750 kcmil380.0 mm²475 A4.08 V (33.97%)7.9 V6.72 V (56.04%)1936.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.06 V (25.48%)8.9 V5.04 V (42.03%)1452.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 250 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 250 feet one-way at 12V (DC), you need 9× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.83%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.04V (42.03%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.