🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 120 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.45%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.42V (20.17%)
Voltage at Load End11.7 VLoss: 0.29 V (139.4 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 120 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A357.5 V (2979.13%)0.0 V589.7 V (4914.17%)169810.2 WDrop/Amp High
12 AWG3.31 mm²20 A224.65 V (1872.08%)0.0 V370.57 V (3088.06%)106708.5 WDrop/Amp High
10 AWG5.26 mm²30 A141.37 V (1178.06%)0.0 V233.19 V (1943.24%)67149.3 WDrop/Amp High
8 AWG8.37 mm²50 A88.84 V (740.33%)0.0 V146.54 V (1221.2%)42199.0 WDrop/Amp High
6 AWG13.3 mm²65 A55.91 V (465.91%)0.0 V92.22 V (768.53%)26556.8 WDrop/Amp High
4 AWG21.15 mm²85 A35.16 V (292.98%)0.0 V57.99 V (483.28%)16700.0 WDrop/Amp High
3 AWG26.67 mm²100 A27.88 V (232.34%)0.0 V45.99 V (383.26%)13243.5 WDrop/Amp High
2 AWG33.62 mm²115 A22.12 V (184.31%)0.0 V36.48 V (304.03%)10505.8 WDrop/Amp High
1 AWG42.41 mm²130 A17.53 V (146.11%)0.0 V28.92 V (241.02%)8328.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.9 V (115.85%)0.0 V22.93 V (191.09%)6603.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.03 V (91.9%)1.0 V18.19 V (151.59%)5238.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.75 V (72.89%)3.3 V14.43 V (120.24%)4154.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.94 V (57.8%)5.1 V11.44 V (95.35%)3294.8 WDrop/Amp High
250 kcmil126.7 mm²255 A5.87 V (48.91%)6.1 V9.68 V (80.67%)2787.7 WDrop/Amp High
300 kcmil152.0 mm²285 A4.89 V (40.77%)7.1 V8.07 V (67.25%)2323.7 WDrop/Amp High
350 kcmil177.3 mm²310 A4.19 V (34.95%)7.8 V6.92 V (57.65%)1992.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.67 V (30.57%)8.3 V6.05 V (50.43%)1742.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.93 V (24.45%)9.1 V4.84 V (40.34%)1393.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.45 V (20.38%)9.6 V4.03 V (33.62%)1161.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.96 V (16.31%)10.0 V3.23 V (26.9%)929.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.47 V (12.23%)10.5 V2.42 V (20.17%)697.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 120 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 120 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (2.45%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.42V (20.17%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.