🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 125 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.52V (21.01%)
Voltage at Load End11.7 VLoss: 0.31 V (145.2 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 125 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A372.39 V (3103.26%)0.0 V614.27 V (5118.92%)176885.7 WDrop/Amp High
12 AWG3.31 mm²20 A234.01 V (1950.08%)0.0 V386.01 V (3216.73%)111154.7 WDrop/Amp High
10 AWG5.26 mm²30 A147.26 V (1227.14%)0.0 V242.91 V (2024.21%)69947.2 WDrop/Amp High
8 AWG8.37 mm²50 A92.54 V (771.18%)0.0 V152.65 V (1272.09%)43957.2 WDrop/Amp High
6 AWG13.3 mm²65 A58.24 V (485.32%)0.0 V96.07 V (800.55%)27663.3 WDrop/Amp High
4 AWG21.15 mm²85 A36.62 V (305.19%)0.0 V60.41 V (503.42%)17395.8 WDrop/Amp High
3 AWG26.67 mm²100 A29.04 V (242.02%)0.0 V47.91 V (399.23%)13795.4 WDrop/Amp High
2 AWG33.62 mm²115 A23.04 V (191.99%)0.0 V38.0 V (316.7%)10943.6 WDrop/Amp High
1 AWG42.41 mm²130 A18.26 V (152.2%)0.0 V30.13 V (251.06%)8675.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.48 V (120.67%)0.0 V23.89 V (199.05%)6878.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.49 V (95.73%)0.5 V18.95 V (157.9%)5456.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.11 V (75.93%)2.9 V15.03 V (125.25%)4328.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.23 V (60.21%)4.8 V11.92 V (99.32%)3432.1 WDrop/Amp High
250 kcmil126.7 mm²255 A6.11 V (50.95%)5.9 V10.08 V (84.04%)2903.9 WDrop/Amp High
300 kcmil152.0 mm²285 A5.1 V (42.47%)6.9 V8.41 V (70.05%)2420.5 WDrop/Amp High
350 kcmil177.3 mm²310 A4.37 V (36.41%)7.6 V7.21 V (60.05%)2075.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.82 V (31.84%)8.2 V6.3 V (52.53%)1815.1 WDrop/Amp High
500 kcmil253.4 mm²380 A3.06 V (25.47%)8.9 V5.04 V (42.02%)1451.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.55 V (21.23%)9.5 V4.2 V (35.02%)1210.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.04 V (16.99%)10.0 V3.36 V (28.02%)968.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.53 V (12.74%)10.5 V2.52 V (21.01%)726.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 125 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 125 feet one-way at 12V (DC), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (2.55%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.52V (21.01%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.