475 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.72%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.4V (3.36%)
Voltage at Load End11.7 VLoss: 0.33 V (154.9 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A59.58 V (496.52%)0.0 V98.28 V (819.03%)28301.7 WDrop/Amp High
12 AWG3.31 mm²20 A37.44 V (312.01%)0.0 V61.76 V (514.68%)17784.8 WDrop/Amp High
10 AWG5.26 mm²30 A23.56 V (196.34%)0.0 V38.86 V (323.87%)11191.5 WDrop/Amp High
8 AWG8.37 mm²50 A14.81 V (123.39%)0.0 V24.42 V (203.53%)7033.2 WDrop/Amp High
6 AWG13.3 mm²65 A9.32 V (77.65%)2.7 V15.37 V (128.09%)4426.1 WDrop/Amp High
4 AWG21.15 mm²85 A5.86 V (48.83%)6.1 V9.67 V (80.55%)2783.3 WDrop/Amp High
3 AWG26.67 mm²100 A4.65 V (38.72%)7.4 V7.67 V (63.88%)2207.3 WDrop/Amp High
2 AWG33.62 mm²115 A3.69 V (30.72%)8.3 V6.08 V (50.67%)1751.0 WDrop/Amp High
1 AWG42.41 mm²130 A2.92 V (24.35%)9.1 V4.82 V (40.17%)1388.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.32 V (19.31%)9.7 V3.82 V (31.85%)1100.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.84 V (15.32%)10.2 V3.03 V (25.26%)873.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.46 V (12.15%)10.5 V2.4 V (20.04%)692.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.16 V (9.63%)10.8 V1.91 V (15.89%)549.1 WDrop/Amp High
250 kcmil126.7 mm²255 A0.98 V (8.15%)11.0 V1.61 V (13.45%)464.6 WDrop/Amp High
300 kcmil152.0 mm²285 A0.82 V (6.79%)11.2 V1.34 V (11.21%)387.3 WDrop/Amp High
350 kcmil177.3 mm²310 A0.7 V (5.82%)11.3 V1.15 V (9.61%)332.0 WDrop/Amp High
400 kcmil202.7 mm²335 A0.61 V (5.1%)11.4 V1.01 V (8.4%)290.4 WDrop/Amp High
500 kcmil253.4 mm²380 A0.49 V (4.08%)11.5 V0.81 V (6.72%)232.3 WDrop/Amp High
600 kcmil304.0 mm²420 A0.41 V (3.4%)11.6 V0.67 V (5.6%)193.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.33 V (2.72%)11.7 V0.54 V (4.48%)154.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.24 V (2.04%)11.8 V0.4 V (3.36%)116.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 20 feet one-way at 12V (DC), you need 750 kcmil copper wire. This produces a voltage drop of 0.33V (2.72%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.4V (3.36%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.