🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.53V (29.42%)
Voltage at Load End11.6 VLoss: 0.36 V (169.4 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A521.35 V (4344.56%)0.0 V859.98 V (7166.49%)247639.9 WDrop/Amp High
12 AWG3.31 mm²20 A327.61 V (2730.12%)0.0 V540.41 V (4503.42%)155616.6 WDrop/Amp High
10 AWG5.26 mm²30 A206.16 V (1718.0%)0.0 V340.07 V (2833.9%)97926.1 WDrop/Amp High
8 AWG8.37 mm²50 A129.56 V (1079.65%)0.0 V213.71 V (1780.92%)61540.1 WDrop/Amp High
6 AWG13.3 mm²65 A81.53 V (679.45%)0.0 V134.49 V (1120.77%)38728.6 WDrop/Amp High
4 AWG21.15 mm²85 A51.27 V (427.27%)0.0 V84.57 V (704.79%)24354.2 WDrop/Amp High
3 AWG26.67 mm²100 A40.66 V (338.83%)0.0 V67.07 V (558.92%)19313.5 WDrop/Amp High
2 AWG33.62 mm²115 A32.25 V (268.79%)0.0 V53.21 V (443.38%)15321.0 WDrop/Amp High
1 AWG42.41 mm²130 A25.57 V (213.08%)0.0 V42.18 V (351.48%)12145.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A20.27 V (168.94%)0.0 V33.44 V (278.67%)9629.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A16.08 V (134.02%)0.0 V26.53 V (221.06%)7638.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.76 V (106.3%)0.0 V21.04 V (175.35%)6059.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A10.12 V (84.3%)1.9 V16.69 V (139.05%)4805.0 WDrop/Amp High
250 kcmil126.7 mm²255 A8.56 V (71.32%)3.4 V14.12 V (117.65%)4065.4 WDrop/Amp High
300 kcmil152.0 mm²285 A7.13 V (59.45%)4.9 V11.77 V (98.07%)3388.8 WDrop/Amp High
350 kcmil177.3 mm²310 A6.12 V (50.97%)5.9 V10.09 V (84.07%)2905.2 WDrop/Amp High
400 kcmil202.7 mm²335 A5.35 V (44.58%)6.7 V8.82 V (73.54%)2541.1 WDrop/Amp High
500 kcmil253.4 mm²380 A4.28 V (35.66%)7.7 V7.06 V (58.83%)2032.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.57 V (29.73%)8.4 V5.88 V (49.03%)1694.4 WDrop/Amp High
750 kcmil380.0 mm²475 A2.85 V (23.78%)9.1 V4.71 V (39.23%)1355.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.14 V (17.83%)9.9 V3.53 V (29.42%)1016.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 175 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (2.97%) and delivers 11.6V at the load.

What size aluminum wire is required for 475 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.53V (29.42%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.