🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.72%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.61V (13.45%)
Voltage at Load End11.7 VLoss: 0.33 V (154.9 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A238.33 V (1986.08%)0.0 V393.13 V (3276.11%)113206.8 WDrop/Amp High
12 AWG3.31 mm²20 A149.77 V (1248.05%)0.0 V247.04 V (2058.7%)71139.0 WDrop/Amp High
10 AWG5.26 mm²30 A94.24 V (785.37%)0.0 V155.46 V (1295.5%)44766.2 WDrop/Amp High
8 AWG8.37 mm²50 A59.23 V (493.56%)0.0 V97.7 V (814.14%)28132.6 WDrop/Amp High
6 AWG13.3 mm²65 A37.27 V (310.61%)0.0 V61.48 V (512.35%)17704.5 WDrop/Amp High
4 AWG21.15 mm²85 A23.44 V (195.32%)0.0 V38.66 V (322.19%)11133.3 WDrop/Amp High
3 AWG26.67 mm²100 A18.59 V (154.9%)0.0 V30.66 V (255.5%)8829.0 WDrop/Amp High
2 AWG33.62 mm²115 A14.74 V (122.87%)0.0 V24.32 V (202.69%)7003.9 WDrop/Amp High
1 AWG42.41 mm²130 A11.69 V (97.41%)0.3 V19.28 V (160.68%)5552.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.27 V (77.23%)2.7 V15.29 V (127.39%)4402.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.35 V (61.26%)4.6 V12.13 V (101.06%)3492.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.83 V (48.59%)6.2 V9.62 V (80.16%)2769.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.62 V (38.54%)7.4 V7.63 V (63.57%)2196.6 WDrop/Amp High
250 kcmil126.7 mm²255 A3.91 V (32.61%)8.1 V6.45 V (53.78%)1858.5 WDrop/Amp High
300 kcmil152.0 mm²285 A3.26 V (27.18%)8.7 V5.38 V (44.83%)1549.1 WDrop/Amp High
350 kcmil177.3 mm²310 A2.8 V (23.3%)9.2 V4.61 V (38.43%)1328.1 WDrop/Amp High
400 kcmil202.7 mm²335 A2.45 V (20.38%)9.6 V4.03 V (33.62%)1161.7 WDrop/Amp High
500 kcmil253.4 mm²380 A1.96 V (16.3%)10.0 V3.23 V (26.89%)929.2 WDrop/Amp High
600 kcmil304.0 mm²420 A1.63 V (13.59%)10.4 V2.69 V (22.42%)774.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.3 V (10.87%)10.7 V2.15 V (17.93%)619.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.98 V (8.15%)11.0 V1.61 V (13.45%)464.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 80 feet one-way at 12V (DC), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.72%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.61V (13.45%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.