475 Amp Wire Size at 150 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)6× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.55%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.03V (25.22%)
Voltage at Load End11.7 VLoss: 0.3 V (145.2 W)
Power & Breaker (125%)5.7 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 150 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A446.87 V (3723.91%)0.0 V737.13 V (6142.71%)212262.8 WDrop/Amp High
12 AWG3.31 mm²20 A280.81 V (2340.1%)0.0 V463.21 V (3860.07%)133385.7 WDrop/Amp High
10 AWG5.26 mm²30 A176.71 V (1472.57%)0.0 V291.49 V (2429.06%)83936.6 WDrop/Amp High
8 AWG8.37 mm²50 A111.05 V (925.42%)0.0 V183.18 V (1526.5%)52748.7 WDrop/Amp High
6 AWG13.3 mm²65 A69.89 V (582.39%)0.0 V115.28 V (960.66%)33196.0 WDrop/Amp High
4 AWG21.15 mm²85 A43.95 V (366.23%)0.0 V72.49 V (604.11%)20875.0 WDrop/Amp High
3 AWG26.67 mm²100 A34.85 V (290.43%)0.0 V57.49 V (479.07%)16554.4 WDrop/Amp High
2 AWG33.62 mm²115 A27.65 V (230.39%)0.0 V45.6 V (380.04%)13132.3 WDrop/Amp High
1 AWG42.41 mm²130 A21.92 V (182.64%)0.0 V36.15 V (301.27%)10410.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.38 V (144.81%)0.0 V28.66 V (238.86%)8254.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.78 V (114.87%)0.0 V22.74 V (189.48%)6547.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.93 V (91.12%)1.1 V18.04 V (150.3%)5193.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.67 V (72.25%)3.3 V14.3 V (119.19%)4118.5 WDrop/Amp High
250 kcmil126.7 mm²255 A7.34 V (61.13%)4.7 V12.1 V (100.84%)3484.7 WDrop/Amp High
300 kcmil152.0 mm²285 A6.12 V (50.96%)5.9 V10.09 V (84.06%)2904.6 WDrop/Amp High
350 kcmil177.3 mm²310 A5.24 V (43.69%)6.8 V8.65 V (72.06%)2490.2 WDrop/Amp High
400 kcmil202.7 mm²335 A4.59 V (38.21%)7.4 V7.56 V (63.03%)2178.1 WDrop/Amp High
500 kcmil253.4 mm²380 A3.67 V (30.57%)8.3 V6.05 V (50.42%)1742.3 WDrop/Amp High
600 kcmil304.0 mm²420 A3.06 V (25.48%)8.9 V5.04 V (42.03%)1452.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.45 V (20.38%)9.6 V4.03 V (33.62%)1161.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.83 V (15.29%)10.2 V3.03 V (25.22%)871.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 150 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 150 feet one-way at 12V (DC), you need 6× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (2.55%) and delivers 11.7V at the load.

What size aluminum wire is required for 475 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.03V (25.22%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.