475 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 0.74%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.37V (0.91%)
Voltage at Load End476.5 VLoss: 3.53 V (2904.6 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A645.0 V (134.37%)0.0 V1063.95 V (221.66%)530657.0 WDrop/Amp High
12 AWG3.31 mm²20 A405.32 V (84.44%)74.7 V668.58 V (139.29%)333464.2 WDrop/Amp High
10 AWG5.26 mm²30 A255.06 V (53.14%)224.9 V420.72 V (87.65%)209841.5 WDrop/Amp High
8 AWG8.37 mm²50 A160.29 V (33.39%)319.7 V264.4 V (55.08%)131871.7 WDrop/Amp High
6 AWG13.3 mm²65 A100.87 V (21.02%)379.1 V166.39 V (34.66%)82990.0 WDrop/Amp High
4 AWG21.15 mm²85 A63.43 V (13.22%)416.6 V104.63 V (21.8%)52187.5 WDrop/Amp High
3 AWG26.67 mm²100 A50.3 V (10.48%)429.7 V82.98 V (17.29%)41386.1 WDrop/Amp High
2 AWG33.62 mm²115 A39.9 V (8.31%)440.1 V65.82 V (13.71%)32830.7 WDrop/Amp High
1 AWG42.41 mm²130 A31.63 V (6.59%)448.4 V52.18 V (10.87%)26026.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.08 V (5.23%)454.9 V41.37 V (8.62%)20635.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A19.9 V (4.15%)460.1 V32.82 V (6.84%)16369.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.78 V (3.29%)464.2 V26.03 V (5.42%)12984.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.51 V (2.61%)467.5 V20.64 V (4.3%)10296.3 WDrop/Amp High
250 kcmil126.7 mm²255 A10.59 V (2.21%)469.4 V17.47 V (3.64%)8711.7 WDrop/Amp High
300 kcmil152.0 mm²285 A8.83 V (1.84%)471.2 V14.56 V (3.03%)7261.6 WDrop/Amp High
350 kcmil177.3 mm²310 A7.57 V (1.58%)472.4 V12.48 V (2.6%)6225.4 WDrop/Amp High
400 kcmil202.7 mm²335 A6.62 V (1.38%)473.4 V10.92 V (2.27%)5445.3 WDrop/Amp High
500 kcmil253.4 mm²380 A5.29 V (1.1%)474.7 V8.73 V (1.82%)4355.8 WDrop/Amp High
600 kcmil304.0 mm²420 A4.41 V (0.92%)475.6 V7.28 V (1.52%)3630.8 WDrop/Amp High
750 kcmil380.0 mm²475 A3.53 V (0.74%)476.5 V5.82 V (1.21%)2904.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A2.65 V (0.55%)477.4 V4.37 V (0.91%)2178.3 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 250 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 3.53V (0.74%) and delivers 476.5V at the load.

What size aluminum wire is required for 475 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.37V (0.91%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.