⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.1V (10.09%)
Voltage at Load End117.5 VLoss: 2.45 V (1161.8 W)
Power & Breaker (125%)57.0 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1787.48 V (1489.56%)0.0 V2948.5 V (2457.08%)849051.2 WDrop/Amp High
12 AWG3.31 mm²20 A1123.25 V (936.04%)0.0 V1852.83 V (1544.03%)533542.7 WDrop/Amp High
10 AWG5.26 mm²30 A706.83 V (589.03%)0.0 V1165.95 V (971.62%)335746.5 WDrop/Amp High
8 AWG8.37 mm²50 A444.2 V (370.17%)0.0 V732.72 V (610.6%)210994.8 WDrop/Amp High
6 AWG13.3 mm²65 A279.55 V (232.95%)0.0 V461.12 V (384.27%)132783.9 WDrop/Amp High
4 AWG21.15 mm²85 A175.79 V (146.49%)0.0 V289.97 V (241.64%)83500.1 WDrop/Amp High
3 AWG26.67 mm²100 A139.41 V (116.17%)0.0 V229.95 V (191.63%)66217.7 WDrop/Amp High
2 AWG33.62 mm²115 A110.59 V (92.16%)9.4 V182.42 V (152.01%)52529.0 WDrop/Amp High
1 AWG42.41 mm²130 A87.67 V (73.06%)32.3 V144.61 V (120.51%)41641.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A69.51 V (57.92%)50.5 V114.65 V (95.55%)33016.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A55.14 V (45.95%)64.9 V90.95 V (75.79%)26190.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A43.74 V (36.45%)76.3 V72.14 V (60.12%)20774.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A34.68 V (28.9%)85.3 V57.21 V (47.67%)16474.1 WDrop/Amp High
250 kcmil126.7 mm²255 A29.34 V (24.45%)90.7 V48.4 V (40.34%)13938.6 WDrop/Amp High
300 kcmil152.0 mm²285 A24.46 V (20.38%)95.5 V40.35 V (33.62%)11618.6 WDrop/Amp High
350 kcmil177.3 mm²310 A20.97 V (17.47%)99.0 V34.59 V (28.83%)9960.7 WDrop/Amp High
400 kcmil202.7 mm²335 A18.34 V (15.29%)101.7 V30.26 V (25.21%)8712.5 WDrop/Amp High
500 kcmil253.4 mm²380 A14.67 V (12.23%)105.3 V24.2 V (20.17%)6969.3 WDrop/Amp High
600 kcmil304.0 mm²420 A12.23 V (10.19%)107.8 V20.17 V (16.81%)5809.3 WDrop/Amp High
750 kcmil380.0 mm²475 A9.78 V (8.15%)110.2 V16.14 V (13.45%)4647.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.34 V (6.11%)112.7 V12.1 V (10.09%)3485.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 600 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.45V (2.04%) and delivers 117.5V at the load.

What size aluminum wire is required for 475 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.1V (10.09%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.