🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

475 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)750 kcmil380.0 mm² · Drop: 2.21%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.1V (2.73%)
Voltage at Load End469.4 VLoss: 10.59 V (8713.9 W)
Power & Breaker (125%)394.91 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1935.0 V (403.12%)0.0 V3191.85 V (664.97%)1591970.9 WDrop/Amp High
12 AWG3.31 mm²20 A1215.95 V (253.32%)0.0 V2005.75 V (417.86%)1000392.6 WDrop/Amp High
10 AWG5.26 mm²30 A765.17 V (159.41%)0.0 V1262.17 V (262.95%)629524.6 WDrop/Amp High
8 AWG8.37 mm²50 A480.86 V (100.18%)0.0 V793.19 V (165.25%)395615.2 WDrop/Amp High
6 AWG13.3 mm²65 A302.62 V (63.05%)177.4 V499.18 V (103.99%)248969.9 WDrop/Amp High
4 AWG21.15 mm²85 A190.3 V (39.65%)289.7 V313.9 V (65.4%)156562.6 WDrop/Amp High
3 AWG26.67 mm²100 A150.91 V (31.44%)329.1 V248.93 V (51.86%)124158.2 WDrop/Amp High
2 AWG33.62 mm²115 A119.71 V (24.94%)360.3 V197.47 V (41.14%)98492.0 WDrop/Amp High
1 AWG42.41 mm²130 A94.9 V (19.77%)385.1 V156.54 V (32.61%)78078.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A75.24 V (15.68%)404.8 V124.12 V (25.86%)61905.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A59.69 V (12.44%)420.3 V98.46 V (20.51%)49107.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A47.35 V (9.86%)432.7 V78.1 V (16.27%)38951.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A37.54 V (7.82%)442.5 V61.93 V (12.9%)30889.0 WDrop/Amp High
250 kcmil126.7 mm²255 A31.77 V (6.62%)448.2 V52.4 V (10.92%)26135.0 WDrop/Amp High
300 kcmil152.0 mm²285 A26.48 V (5.52%)453.5 V43.68 V (9.1%)21784.9 WDrop/Amp High
350 kcmil177.3 mm²310 A22.7 V (4.73%)457.3 V37.45 V (7.8%)18676.3 WDrop/Amp High
400 kcmil202.7 mm²335 A19.86 V (4.14%)460.1 V32.75 V (6.82%)16336.0 WDrop/Amp High
500 kcmil253.4 mm²380 A15.88 V (3.31%)464.1 V26.2 V (5.46%)13067.5 WDrop/Amp High
600 kcmil304.0 mm²420 A13.24 V (2.76%)466.8 V21.84 V (4.55%)10892.4 WDrop/Amp High
750 kcmil380.0 mm²475 A10.59 V (2.21%)469.4 V17.47 V (3.64%)8713.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A7.94 V (1.65%)472.1 V13.1 V (2.73%)6535.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 750 feet one-way at 480V (3-Phase), you need 750 kcmil copper wire. This produces a voltage drop of 10.59V (2.21%) and delivers 469.4V at the load.

What size aluminum wire is required for 475 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.1V (2.73%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.