475 Amp Wire Size at 800 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 475 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.98V (6.72%)
Voltage at Load End203.8 VLoss: 4.24 V (3485.3 W)
Power & Breaker (125%)171.13 kW600A Breaker Recommended

All AWG & kcmil Wire Gauges for 475 Amps at 800 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2064.0 V (992.31%)0.0 V3404.63 V (1636.84%)1698102.3 WDrop/Amp High
12 AWG3.31 mm²20 A1297.01 V (623.56%)0.0 V2139.47 V (1028.59%)1067085.5 WDrop/Amp High
10 AWG5.26 mm²30 A816.18 V (392.4%)0.0 V1346.32 V (647.27%)671492.9 WDrop/Amp High
8 AWG8.37 mm²50 A512.92 V (246.59%)0.0 V846.07 V (406.77%)421989.6 WDrop/Amp High
6 AWG13.3 mm²65 A322.79 V (155.19%)0.0 V532.45 V (255.99%)265567.9 WDrop/Amp High
4 AWG21.15 mm²85 A202.98 V (97.59%)5.0 V334.83 V (160.98%)167000.1 WDrop/Amp High
3 AWG26.67 mm²100 A160.97 V (77.39%)47.0 V265.53 V (127.66%)132435.4 WDrop/Amp High
2 AWG33.62 mm²115 A127.7 V (61.39%)80.3 V210.64 V (101.27%)105058.1 WDrop/Amp High
1 AWG42.41 mm²130 A101.23 V (48.67%)106.8 V166.98 V (80.28%)83283.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A80.26 V (38.59%)127.7 V132.39 V (63.65%)66032.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A63.67 V (30.61%)144.3 V105.02 V (50.49%)52381.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A50.5 V (24.28%)157.5 V83.3 V (40.05%)41548.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A40.05 V (19.25%)168.0 V66.06 V (31.76%)32948.3 WDrop/Amp High
250 kcmil126.7 mm²255 A33.88 V (16.29%)174.1 V55.89 V (26.87%)27877.3 WDrop/Amp High
300 kcmil152.0 mm²285 A28.24 V (13.58%)179.8 V46.59 V (22.4%)23237.2 WDrop/Amp High
350 kcmil177.3 mm²310 A24.21 V (11.64%)183.8 V39.94 V (19.2%)19921.3 WDrop/Amp High
400 kcmil202.7 mm²335 A21.18 V (10.18%)186.8 V34.94 V (16.8%)17425.0 WDrop/Amp High
500 kcmil253.4 mm²380 A16.94 V (8.15%)191.1 V27.95 V (13.44%)13938.6 WDrop/Amp High
600 kcmil304.0 mm²420 A14.12 V (6.79%)193.9 V23.29 V (11.2%)11618.6 WDrop/Amp High
750 kcmil380.0 mm²475 A11.3 V (5.43%)196.7 V18.64 V (8.96%)9294.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.47 V (4.07%)199.5 V13.98 V (6.72%)6970.7 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 475 amps at 800 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 475A load over 800 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.24V (2.04%) and delivers 203.8V at the load.

What size aluminum wire is required for 475 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.98V (6.72%).

What breaker size is needed for a 475A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (475A × 1.25 = 593.8A), which corresponds to a standard 600A circuit breaker.