🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 450 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.1V (3.79%)
Voltage at Load End237.2 VLoss: 2.76 V (2628.5 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1344.32 V (560.13%)0.0 V2217.49 V (923.96%)1280632.6 WDrop/Amp High
12 AWG3.31 mm²20 A844.77 V (351.99%)0.0 V1393.47 V (580.61%)804748.0 WDrop/Amp High
10 AWG5.26 mm²30 A531.59 V (221.5%)0.0 V876.88 V (365.37%)506409.8 WDrop/Amp High
8 AWG8.37 mm²50 A334.07 V (139.2%)0.0 V551.06 V (229.61%)318245.6 WDrop/Amp High
6 AWG13.3 mm²65 A210.24 V (87.6%)29.8 V346.8 V (144.5%)200279.4 WDrop/Amp High
4 AWG21.15 mm²85 A132.21 V (55.09%)107.8 V218.08 V (90.87%)125944.0 WDrop/Amp High
3 AWG26.67 mm²100 A104.84 V (43.68%)135.2 V172.94 V (72.06%)99876.9 WDrop/Amp High
2 AWG33.62 mm²115 A83.17 V (34.65%)156.8 V137.19 V (57.16%)79230.1 WDrop/Amp High
1 AWG42.41 mm²130 A65.93 V (27.47%)174.1 V108.76 V (45.32%)62808.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A52.27 V (21.78%)187.7 V86.23 V (35.93%)49798.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.47 V (17.28%)198.5 V68.4 V (28.5%)39503.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.89 V (13.71%)207.1 V54.26 V (22.61%)31334.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.08 V (10.87%)213.9 V43.03 V (17.93%)24848.1 WDrop/Amp High
250 kcmil126.7 mm²255 A22.07 V (9.2%)217.9 V36.4 V (15.17%)21023.8 WDrop/Amp High
300 kcmil152.0 mm²285 A18.4 V (7.66%)221.6 V30.34 V (12.64%)17524.4 WDrop/Amp High
350 kcmil177.3 mm²310 A15.77 V (6.57%)224.2 V26.01 V (10.84%)15023.8 WDrop/Amp High
400 kcmil202.7 mm²335 A13.79 V (5.75%)226.2 V22.75 V (9.48%)13141.2 WDrop/Amp High
500 kcmil253.4 mm²380 A11.03 V (4.6%)229.0 V18.2 V (7.58%)10511.9 WDrop/Amp High
600 kcmil304.0 mm²420 A9.2 V (3.83%)230.8 V15.17 V (6.32%)8762.2 WDrop/Amp High
750 kcmil380.0 mm²475 A7.36 V (3.07%)232.6 V12.14 V (5.06%)7009.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.52 V (2.3%)234.5 V9.1 V (3.79%)5257.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 450 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.76V (1.15%) and delivers 237.2V at the load.

What size aluminum wire is required for 550 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.1V (3.79%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.