🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

60 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 60 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.91%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 5.75V (2.4%)
Voltage at Load End233.0 VLoss: 6.99 V (726.4 W)
Power & Breaker (125%)24.94 kW80A Breaker Recommended

All AWG & kcmil Wire Gauges for 60 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A89.62 V (37.34%)150.4 V147.83 V (61.6%)9313.7 WDrop/Amp High
12 AWG3.31 mm²20 A56.32 V (23.47%)183.7 V92.9 V (38.71%)5852.7 WDrop/Amp High
10 AWG5.26 mm²30 A35.44 V (14.77%)204.6 V58.46 V (24.36%)3683.0 WDrop/Amp High
8 AWG8.37 mm²50 A22.27 V (9.28%)217.7 V36.74 V (15.31%)2314.5 WDrop/Amp High
6 AWG13.3 mm²65 A14.02 V (5.84%)226.0 V23.12 V (9.63%)1456.6 WDrop/Amp High
4 AWG21.15 mm²85 A8.81 V (3.67%)231.2 V14.54 V (6.06%)916.0 W~ ≤5%
3 AWG26.67 mm²100 A6.99 V (2.91%)233.0 V11.53 V (4.8%)726.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A5.54 V (2.31%)234.5 V9.15 V (3.81%)576.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.4 V (1.83%)235.6 V7.25 V (3.02%)456.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.48 V (1.45%)236.5 V5.75 V (2.4%)362.2 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.76 V (1.15%)237.2 V4.56 V (1.9%)287.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.19 V (0.91%)237.8 V3.62 V (1.51%)227.9 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.74 V (0.72%)238.3 V2.87 V (1.2%)180.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.47 V (0.61%)238.5 V2.43 V (1.01%)152.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.23 V (0.51%)238.8 V2.02 V (0.84%)127.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.05 V (0.44%)238.9 V1.73 V (0.72%)109.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.92 V (0.38%)239.1 V1.52 V (0.63%)95.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.74 V (0.31%)239.3 V1.21 V (0.51%)76.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.61 V (0.26%)239.4 V1.01 V (0.42%)63.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.49 V (0.2%)239.5 V0.81 V (0.34%)51.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.37 V (0.15%)239.6 V0.61 V (0.25%)38.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 60 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 60A load over 275 feet one-way at 240V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 6.99V (2.91%) and delivers 233.0V at the load.

What size aluminum wire is required for 60 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 5.75V (2.4%).

What breaker size is needed for a 60A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (60A × 1.25 = 75.0A), which corresponds to a standard 80A circuit breaker.