⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

150 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 150 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.88%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 7.17V (2.99%)
Voltage at Load End233.1 VLoss: 6.91 V (1795.6 W)
Power & Breaker (125%)62.35 kW200A Breaker Recommended

All AWG & kcmil Wire Gauges for 150 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A224.05 V (93.36%)15.9 V369.58 V (153.99%)58210.6 WDrop/Amp High
12 AWG3.31 mm²20 A140.79 V (58.66%)99.2 V232.24 V (96.77%)36579.5 WDrop/Amp High
10 AWG5.26 mm²30 A88.6 V (36.92%)151.4 V146.15 V (60.89%)23018.6 WDrop/Amp High
8 AWG8.37 mm²50 A55.68 V (23.2%)184.3 V91.84 V (38.27%)14465.7 WDrop/Amp High
6 AWG13.3 mm²65 A35.04 V (14.6%)205.0 V57.8 V (24.08%)9103.6 WDrop/Amp High
4 AWG21.15 mm²85 A22.03 V (9.18%)218.0 V36.35 V (15.14%)5724.7 WDrop/Amp High
3 AWG26.67 mm²100 A17.47 V (7.28%)222.5 V28.82 V (12.01%)4539.9 WDrop/Amp High
2 AWG33.62 mm²115 A13.86 V (5.78%)226.1 V22.87 V (9.53%)3601.4 WDrop/Amp High
1 AWG42.41 mm²130 A10.99 V (4.58%)229.0 V18.13 V (7.55%)2854.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A8.71 V (3.63%)231.3 V14.37 V (5.99%)2263.6 W~ ≤5%
2/0 AWG67.43 mm²175 A6.91 V (2.88%)233.1 V11.4 V (4.75%)1795.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.48 V (2.28%)234.5 V9.04 V (3.77%)1424.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.35 V (1.81%)235.7 V7.17 V (2.99%)1129.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.68 V (1.53%)236.3 V6.07 V (2.53%)955.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.07 V (1.28%)236.9 V5.06 V (2.11%)796.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.63 V (1.1%)237.4 V4.34 V (1.81%)682.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.3 V (0.96%)237.7 V3.79 V (1.58%)597.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.84 V (0.77%)238.2 V3.03 V (1.26%)477.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.53 V (0.64%)238.5 V2.53 V (1.05%)398.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.23 V (0.51%)238.8 V2.02 V (0.84%)318.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.92 V (0.38%)239.1 V1.52 V (0.63%)239.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 150 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 150A load over 275 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 6.91V (2.88%) and delivers 233.1V at the load.

What size aluminum wire is required for 150 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 7.17V (2.99%).

What breaker size is needed for a 150A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (150A × 1.25 = 187.5A), which corresponds to a standard 200A circuit breaker.