🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 6.03V (2.51%)
Voltage at Load End234.2 VLoss: 5.81 V (1006.0 W)
Power & Breaker (125%)41.57 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A149.37 V (62.24%)90.6 V246.39 V (102.66%)25871.4 WDrop/Amp High
12 AWG3.31 mm²20 A93.86 V (39.11%)146.1 V154.83 V (64.51%)16257.5 WDrop/Amp High
10 AWG5.26 mm²30 A59.07 V (24.61%)180.9 V97.43 V (40.6%)10230.5 WDrop/Amp High
8 AWG8.37 mm²50 A37.12 V (15.47%)202.9 V61.23 V (25.51%)6429.2 WDrop/Amp High
6 AWG13.3 mm²65 A23.36 V (9.73%)216.6 V38.53 V (16.06%)4046.0 WDrop/Amp High
4 AWG21.15 mm²85 A14.69 V (6.12%)225.3 V24.23 V (10.1%)2544.3 WDrop/Amp High
3 AWG26.67 mm²100 A11.65 V (4.85%)228.4 V19.22 V (8.01%)2017.7 W~ ≤5%
2 AWG33.62 mm²115 A9.24 V (3.85%)230.8 V15.24 V (6.35%)1600.6 W~ ≤5%
1 AWG42.41 mm²130 A7.33 V (3.05%)232.7 V12.08 V (5.04%)1268.9 W~ ≤5%
1/0 AWG53.49 mm²150 A5.81 V (2.42%)234.2 V9.58 V (3.99%)1006.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.61 V (1.92%)235.4 V7.6 V (3.17%)798.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.65 V (1.52%)236.3 V6.03 V (2.51%)633.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.9 V (1.21%)237.1 V4.78 V (1.99%)502.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.45 V (1.02%)237.5 V4.04 V (1.69%)424.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.04 V (0.85%)238.0 V3.37 V (1.4%)354.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.75 V (0.73%)238.2 V2.89 V (1.2%)303.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.53 V (0.64%)238.5 V2.53 V (1.05%)265.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.23 V (0.51%)238.8 V2.02 V (0.84%)212.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.02 V (0.43%)239.0 V1.69 V (0.7%)177.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.82 V (0.34%)239.2 V1.35 V (0.56%)141.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.61 V (0.26%)239.4 V1.01 V (0.42%)106.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 275 feet one-way at 240V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 5.81V (2.42%) and delivers 234.2V at the load.

What size aluminum wire is required for 100 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 6.03V (2.51%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.