🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.4%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.98V (2.49%)
Voltage at Load End234.2 VLoss: 5.76 V (1247.0 W)
Power & Breaker (125%)51.96 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A186.71 V (77.8%)53.3 V307.99 V (128.33%)40424.0 WDrop/Amp High
12 AWG3.31 mm²20 A117.33 V (48.89%)122.7 V193.54 V (80.64%)25402.4 WDrop/Amp High
10 AWG5.26 mm²30 A73.83 V (30.76%)166.2 V121.79 V (50.75%)15985.2 WDrop/Amp High
8 AWG8.37 mm²50 A46.4 V (19.33%)193.6 V76.54 V (31.89%)10045.6 WDrop/Amp High
6 AWG13.3 mm²65 A29.2 V (12.17%)210.8 V48.17 V (20.07%)6322.0 WDrop/Amp High
4 AWG21.15 mm²85 A18.36 V (7.65%)221.6 V30.29 V (12.62%)3975.5 WDrop/Amp High
3 AWG26.67 mm²100 A14.56 V (6.07%)225.4 V24.02 V (10.01%)3152.7 WDrop/Amp High
2 AWG33.62 mm²115 A11.55 V (4.81%)228.4 V19.05 V (7.94%)2500.9 WDrop/Amp High
1 AWG42.41 mm²130 A9.16 V (3.82%)230.8 V15.11 V (6.29%)1982.6 W~ ≤5%
1/0 AWG53.49 mm²150 A7.26 V (3.03%)232.7 V11.98 V (4.99%)1571.9 W~ ≤5%
2/0 AWG67.43 mm²175 A5.76 V (2.4%)234.2 V9.5 V (3.96%)1247.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.57 V (1.9%)235.4 V7.54 V (3.14%)989.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.62 V (1.51%)236.4 V5.98 V (2.49%)784.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.07 V (1.28%)236.9 V5.06 V (2.11%)663.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.55 V (1.06%)237.4 V4.21 V (1.76%)553.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.19 V (0.91%)237.8 V3.61 V (1.51%)474.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.92 V (0.8%)238.1 V3.16 V (1.32%)414.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.53 V (0.64%)238.5 V2.53 V (1.05%)331.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.28 V (0.53%)238.7 V2.11 V (0.88%)276.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.02 V (0.43%)239.0 V1.69 V (0.7%)221.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.77 V (0.32%)239.2 V1.26 V (0.53%)165.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 275 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.76V (2.4%) and delivers 234.2V at the load.

What size aluminum wire is required for 125 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.98V (2.49%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.