⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1 AWG42.41 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)2/0 AWGDrop: 6.08V (2.53%)
Voltage at Load End234.1 VLoss: 5.86 V (812.1 W)
Power & Breaker (125%)33.26 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A119.49 V (49.79%)120.5 V197.11 V (82.13%)16557.7 WDrop/Amp High
12 AWG3.31 mm²20 A75.09 V (31.29%)164.9 V123.86 V (51.61%)10404.8 WDrop/Amp High
10 AWG5.26 mm²30 A47.25 V (19.69%)192.7 V77.94 V (32.48%)6547.5 WDrop/Amp High
8 AWG8.37 mm²50 A29.7 V (12.37%)210.3 V48.98 V (20.41%)4114.7 WDrop/Amp High
6 AWG13.3 mm²65 A18.69 V (7.79%)221.3 V30.83 V (12.84%)2589.5 WDrop/Amp High
4 AWG21.15 mm²85 A11.75 V (4.9%)228.2 V19.38 V (8.08%)1628.4 W~ ≤5%
3 AWG26.67 mm²100 A9.32 V (3.88%)230.7 V15.37 V (6.41%)1291.3 W~ ≤5%
2 AWG33.62 mm²115 A7.39 V (3.08%)232.6 V12.19 V (5.08%)1024.4 W~ ≤5%
1 AWG42.41 mm²130 A5.86 V (2.44%)234.1 V9.67 V (4.03%)812.1 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A4.65 V (1.94%)235.4 V7.66 V (3.19%)643.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A3.69 V (1.54%)236.3 V6.08 V (2.53%)510.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.92 V (1.22%)237.1 V4.82 V (2.01%)405.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.32 V (0.97%)237.7 V3.82 V (1.59%)321.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.96 V (0.82%)238.0 V3.24 V (1.35%)271.8 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.64 V (0.68%)238.4 V2.7 V (1.12%)226.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.4 V (0.58%)238.6 V2.31 V (0.96%)194.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.23 V (0.51%)238.8 V2.02 V (0.84%)169.9 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.98 V (0.41%)239.0 V1.62 V (0.67%)135.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.82 V (0.34%)239.2 V1.35 V (0.56%)113.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.65 V (0.27%)239.3 V1.08 V (0.45%)90.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.49 V (0.2%)239.5 V0.81 V (0.34%)68.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 275 feet one-way at 240V (3-Phase), you need 1 AWG copper wire. This produces a voltage drop of 5.86V (2.44%) and delivers 234.1V at the load.

What size aluminum wire is required for 80 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 2/0 AWG to maintain voltage drop at 6.08V (2.53%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.