🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 275 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.32%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.78V (2.41%)
Voltage at Load End234.4 VLoss: 5.57 V (144.7 W)
Power & Breaker (125%)6.24 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 275 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A22.41 V (9.34%)217.6 V36.96 V (15.4%)582.1 WDrop/Amp High
12 AWG3.31 mm²20 A14.08 V (5.87%)225.9 V23.22 V (9.68%)365.8 WDrop/Amp High
10 AWG5.26 mm²30 A8.86 V (3.69%)231.1 V14.61 V (6.09%)230.2 W~ ≤5%
8 AWG8.37 mm²50 A5.57 V (2.32%)234.4 V9.18 V (3.83%)144.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.5 V (1.46%)236.5 V5.78 V (2.41%)91.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.2 V (0.92%)237.8 V3.63 V (1.51%)57.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.75 V (0.73%)238.3 V2.88 V (1.2%)45.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.39 V (0.58%)238.6 V2.29 V (0.95%)36.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.1 V (0.46%)238.9 V1.81 V (0.76%)28.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.87 V (0.36%)239.1 V1.44 V (0.6%)22.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.69 V (0.29%)239.3 V1.14 V (0.48%)18.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.55 V (0.23%)239.5 V0.9 V (0.38%)14.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.43 V (0.18%)239.6 V0.72 V (0.3%)11.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.37 V (0.15%)239.6 V0.61 V (0.25%)9.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.31 V (0.13%)239.7 V0.51 V (0.21%)8.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (0.11%)239.7 V0.43 V (0.18%)6.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.1%)239.8 V0.38 V (0.16%)6.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.18 V (0.08%)239.8 V0.3 V (0.13%)4.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.06%)239.8 V0.25 V (0.11%)4.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.05%)239.9 V0.2 V (0.08%)3.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.04%)239.9 V0.15 V (0.06%)2.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 275 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 275 feet one-way at 240V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.57V (2.32%) and delivers 234.4V at the load.

What size aluminum wire is required for 15 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.78V (2.41%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.