🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.97%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.72V (3.22%)
Voltage at Load End237.7 VLoss: 2.34 V (2433.0 W)
Power & Breaker (125%)249.42 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1140.63 V (475.26%)0.0 V1881.51 V (783.96%)1185378.9 WDrop/Amp High
12 AWG3.31 mm²20 A716.77 V (298.65%)0.0 V1182.34 V (492.64%)744890.7 WDrop/Amp High
10 AWG5.26 mm²30 A451.05 V (187.94%)0.0 V744.02 V (310.01%)468743.0 WDrop/Amp High
8 AWG8.37 mm²50 A283.45 V (118.11%)0.0 V467.57 V (194.82%)294574.5 WDrop/Amp High
6 AWG13.3 mm²65 A178.38 V (74.33%)61.6 V294.25 V (122.6%)185382.6 WDrop/Amp High
4 AWG21.15 mm²85 A112.18 V (46.74%)127.8 V185.04 V (77.1%)116576.3 WDrop/Amp High
3 AWG26.67 mm²100 A88.96 V (37.07%)151.0 V146.74 V (61.14%)92448.0 WDrop/Amp High
2 AWG33.62 mm²115 A70.57 V (29.4%)169.4 V116.41 V (48.5%)73336.9 WDrop/Amp High
1 AWG42.41 mm²130 A55.94 V (23.31%)184.1 V92.28 V (38.45%)58137.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A44.35 V (18.48%)195.6 V73.16 V (30.48%)46094.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A35.18 V (14.66%)204.8 V58.04 V (24.18%)36565.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A27.91 V (11.63%)212.1 V46.04 V (19.18%)29003.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A22.13 V (9.22%)217.9 V36.51 V (15.21%)22999.9 WDrop/Amp High
250 kcmil126.7 mm²255 A18.73 V (7.8%)221.3 V30.89 V (12.87%)19460.0 WDrop/Amp High
300 kcmil152.0 mm²285 A15.61 V (6.5%)224.4 V25.75 V (10.73%)16221.0 WDrop/Amp High
350 kcmil177.3 mm²310 A13.38 V (5.58%)226.6 V22.07 V (9.2%)13906.3 WDrop/Amp High
400 kcmil202.7 mm²335 A11.7 V (4.88%)228.3 V19.31 V (8.04%)12163.7 WDrop/Amp High
500 kcmil253.4 mm²380 A9.36 V (3.9%)230.6 V15.44 V (6.44%)9730.0 WDrop/Amp High
600 kcmil304.0 mm²420 A7.8 V (3.25%)232.2 V12.87 V (5.36%)8110.5 WDrop/Amp High
750 kcmil380.0 mm²475 A6.24 V (2.6%)233.8 V10.3 V (4.29%)6488.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.68 V (1.95%)235.3 V7.72 V (3.22%)4866.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 350 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.34V (0.97%) and delivers 237.7V at the load.

What size aluminum wire is required for 600 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.72V (3.22%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.