🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 20 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.03%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.48V (0.1%)
Voltage at Load End479.9 VLoss: 0.14 V (163.2 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 20 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A70.61 V (14.71%)409.4 V116.47 V (24.27%)79495.6 WDrop/Amp High
12 AWG3.31 mm²20 A44.37 V (9.24%)435.6 V73.19 V (15.25%)49955.0 WDrop/Amp High
10 AWG5.26 mm²30 A27.92 V (5.82%)452.1 V46.06 V (9.6%)31435.5 WDrop/Amp High
8 AWG8.37 mm²50 A17.55 V (3.66%)462.5 V28.94 V (6.03%)19755.2 WDrop/Amp High
6 AWG13.3 mm²65 A11.04 V (2.3%)469.0 V18.22 V (3.79%)12432.4 WDrop/Amp High
4 AWG21.15 mm²85 A6.94 V (1.45%)473.1 V11.45 V (2.39%)7818.0 WDrop/Amp High
3 AWG26.67 mm²100 A5.51 V (1.15%)474.5 V9.08 V (1.89%)6199.9 WDrop/Amp High
2 AWG33.62 mm²115 A4.37 V (0.91%)475.6 V7.21 V (1.5%)4918.2 WDrop/Amp High
1 AWG42.41 mm²130 A3.46 V (0.72%)476.5 V5.71 V (1.19%)3898.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.75 V (0.57%)477.3 V4.53 V (0.94%)3091.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.18 V (0.45%)477.8 V3.59 V (0.75%)2452.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.73 V (0.36%)478.3 V2.85 V (0.59%)1945.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.37 V (0.29%)478.6 V2.26 V (0.47%)1542.5 WDrop/Amp High
250 kcmil126.7 mm²255 A1.16 V (0.24%)478.8 V1.91 V (0.4%)1305.1 WDrop/Amp High
300 kcmil152.0 mm²285 A0.97 V (0.2%)479.0 V1.59 V (0.33%)1087.8 WDrop/Amp High
350 kcmil177.3 mm²310 A0.83 V (0.17%)479.2 V1.37 V (0.28%)932.6 WDrop/Amp High
400 kcmil202.7 mm²335 A0.72 V (0.15%)479.3 V1.2 V (0.25%)815.7 WDrop/Amp High
500 kcmil253.4 mm²380 A0.58 V (0.12%)479.4 V0.96 V (0.2%)652.5 WDrop/Amp High
600 kcmil304.0 mm²420 A0.48 V (0.1%)479.5 V0.8 V (0.17%)543.9 WDrop/Amp High
750 kcmil380.0 mm²475 A0.39 V (0.08%)479.6 V0.64 V (0.13%)435.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.29 V (0.06%)479.7 V0.48 V (0.1%)326.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 20 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 20 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.14V (0.03%) and delivers 479.9V at the load.

What size aluminum wire is required for 650 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.48V (0.1%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.