⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 75 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.79V (0.37%)
Voltage at Load End479.4 VLoss: 0.55 V (611.9 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 75 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A264.79 V (55.16%)215.2 V436.78 V (91.0%)298108.7 WDrop/Amp High
12 AWG3.31 mm²20 A166.39 V (34.67%)313.6 V274.47 V (57.18%)187331.1 WDrop/Amp High
10 AWG5.26 mm²30 A104.71 V (21.81%)375.3 V172.72 V (35.98%)117883.3 WDrop/Amp High
8 AWG8.37 mm²50 A65.8 V (13.71%)414.2 V108.54 V (22.61%)74082.0 WDrop/Amp High
6 AWG13.3 mm²65 A41.41 V (8.63%)438.6 V68.31 V (14.23%)46621.5 WDrop/Amp High
4 AWG21.15 mm²85 A26.04 V (5.43%)454.0 V42.96 V (8.95%)29317.5 WDrop/Amp High
3 AWG26.67 mm²100 A20.65 V (4.3%)459.3 V34.06 V (7.1%)23249.6 WDrop/Amp High
2 AWG33.62 mm²115 A16.38 V (3.41%)463.6 V27.02 V (5.63%)18443.4 WDrop/Amp High
1 AWG42.41 mm²130 A12.99 V (2.71%)467.0 V21.42 V (4.46%)14620.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.3 V (2.15%)469.7 V16.98 V (3.54%)11592.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.17 V (1.7%)471.8 V13.47 V (2.81%)9195.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.48 V (1.35%)473.5 V10.69 V (2.23%)7294.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.14 V (1.07%)474.9 V8.47 V (1.77%)5784.2 WDrop/Amp High
250 kcmil126.7 mm²255 A4.35 V (0.91%)475.7 V7.17 V (1.49%)4894.0 WDrop/Amp High
300 kcmil152.0 mm²285 A3.62 V (0.75%)476.4 V5.98 V (1.25%)4079.4 WDrop/Amp High
350 kcmil177.3 mm²310 A3.11 V (0.65%)476.9 V5.12 V (1.07%)3497.3 WDrop/Amp High
400 kcmil202.7 mm²335 A2.72 V (0.57%)477.3 V4.48 V (0.93%)3059.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.17 V (0.45%)477.8 V3.59 V (0.75%)2447.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.81 V (0.38%)478.2 V2.99 V (0.62%)2039.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.45 V (0.3%)478.6 V2.39 V (0.5%)1631.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.09 V (0.23%)478.9 V1.79 V (0.37%)1223.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 75 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 75 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.55V (0.12%) and delivers 479.4V at the load.

What size aluminum wire is required for 650 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.79V (0.37%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.