🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.18%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.87V (0.6%)
Voltage at Load End479.1 VLoss: 0.87 V (979.0 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A423.66 V (88.26%)56.3 V698.85 V (145.59%)476973.9 WDrop/Amp High
12 AWG3.31 mm²20 A266.23 V (55.46%)213.8 V439.15 V (91.49%)299729.8 WDrop/Amp High
10 AWG5.26 mm²30 A167.53 V (34.9%)312.5 V276.35 V (57.57%)188613.3 WDrop/Amp High
8 AWG8.37 mm²50 A105.28 V (21.93%)374.7 V173.67 V (36.18%)118531.1 WDrop/Amp High
6 AWG13.3 mm²65 A66.26 V (13.8%)413.7 V109.29 V (22.77%)74594.4 WDrop/Amp High
4 AWG21.15 mm²85 A41.67 V (8.68%)438.3 V68.73 V (14.32%)46908.1 WDrop/Amp High
3 AWG26.67 mm²100 A33.04 V (6.88%)447.0 V54.5 V (11.35%)37199.3 WDrop/Amp High
2 AWG33.62 mm²115 A26.21 V (5.46%)453.8 V43.24 V (9.01%)29509.4 WDrop/Amp High
1 AWG42.41 mm²130 A20.78 V (4.33%)459.2 V34.27 V (7.14%)23393.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A16.47 V (3.43%)463.5 V27.18 V (5.66%)18547.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A13.07 V (2.72%)466.9 V21.56 V (4.49%)14713.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A10.37 V (2.16%)469.6 V17.1 V (3.56%)11670.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.22 V (1.71%)471.8 V13.56 V (2.82%)9254.7 WDrop/Amp High
250 kcmil126.7 mm²255 A6.96 V (1.45%)473.0 V11.47 V (2.39%)7830.4 WDrop/Amp High
300 kcmil152.0 mm²285 A5.8 V (1.21%)474.2 V9.56 V (1.99%)6527.0 WDrop/Amp High
350 kcmil177.3 mm²310 A4.97 V (1.04%)475.0 V8.2 V (1.71%)5595.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.35 V (0.91%)475.7 V7.17 V (1.49%)4894.5 WDrop/Amp High
500 kcmil253.4 mm²380 A3.48 V (0.72%)476.5 V5.74 V (1.2%)3915.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.9 V (0.6%)477.1 V4.78 V (1.0%)3263.5 WDrop/Amp High
750 kcmil380.0 mm²475 A2.32 V (0.48%)477.7 V3.83 V (0.8%)2610.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.74 V (0.36%)478.3 V2.87 V (0.6%)1958.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 120 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.87V (0.18%) and delivers 479.1V at the load.

What size aluminum wire is required for 650 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.87V (0.6%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.