⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.39V (0.5%)
Voltage at Load End479.3 VLoss: 0.72 V (815.8 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A353.05 V (73.55%)126.9 V582.37 V (121.33%)397478.2 WDrop/Amp High
12 AWG3.31 mm²20 A221.86 V (46.22%)258.1 V365.96 V (76.24%)249774.9 WDrop/Amp High
10 AWG5.26 mm²30 A139.61 V (29.09%)340.4 V230.29 V (47.98%)157177.7 WDrop/Amp High
8 AWG8.37 mm²50 A87.74 V (18.28%)392.3 V144.72 V (30.15%)98776.0 WDrop/Amp High
6 AWG13.3 mm²65 A55.21 V (11.5%)424.8 V91.08 V (18.97%)62162.0 WDrop/Amp High
4 AWG21.15 mm²85 A34.72 V (7.23%)445.3 V57.27 V (11.93%)39090.1 WDrop/Amp High
3 AWG26.67 mm²100 A27.53 V (5.74%)452.5 V45.42 V (9.46%)30999.4 WDrop/Amp High
2 AWG33.62 mm²115 A21.84 V (4.55%)458.2 V36.03 V (7.51%)24591.2 WDrop/Amp High
1 AWG42.41 mm²130 A17.32 V (3.61%)462.7 V28.56 V (5.95%)19494.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.73 V (2.86%)466.3 V22.65 V (4.72%)15456.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.89 V (2.27%)469.1 V17.96 V (3.74%)12260.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.64 V (1.8%)471.4 V14.25 V (2.97%)9725.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.85 V (1.43%)473.1 V11.3 V (2.35%)7712.3 WDrop/Amp High
250 kcmil126.7 mm²255 A5.8 V (1.21%)474.2 V9.56 V (1.99%)6525.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.83 V (1.01%)475.2 V7.97 V (1.66%)5439.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.14 V (0.86%)475.9 V6.83 V (1.42%)4663.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.62 V (0.75%)476.4 V5.98 V (1.24%)4078.7 WDrop/Amp High
500 kcmil253.4 mm²380 A2.9 V (0.6%)477.1 V4.78 V (1.0%)3262.6 WDrop/Amp High
600 kcmil304.0 mm²420 A2.42 V (0.5%)477.6 V3.98 V (0.83%)2719.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.93 V (0.4%)478.1 V3.19 V (0.66%)2175.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.45 V (0.3%)478.6 V2.39 V (0.5%)1631.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 100 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.72V (0.15%) and delivers 479.3V at the load.

What size aluminum wire is required for 650 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.39V (0.5%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.