⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 40 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.06%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.96V (0.2%)
Voltage at Load End479.7 VLoss: 0.29 V (326.4 W)
Power & Breaker (125%)540.4 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 40 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A141.22 V (29.42%)338.8 V232.95 V (48.53%)158991.3 WDrop/Amp High
12 AWG3.31 mm²20 A88.74 V (18.49%)391.3 V146.38 V (30.5%)99909.9 WDrop/Amp High
10 AWG5.26 mm²30 A55.84 V (11.63%)424.2 V92.12 V (19.19%)62871.1 WDrop/Amp High
8 AWG8.37 mm²50 A35.09 V (7.31%)444.9 V57.89 V (12.06%)39510.4 WDrop/Amp High
6 AWG13.3 mm²65 A22.09 V (4.6%)457.9 V36.43 V (7.59%)24864.8 WDrop/Amp High
4 AWG21.15 mm²85 A13.89 V (2.89%)466.1 V22.91 V (4.77%)15636.0 WDrop/Amp High
3 AWG26.67 mm²100 A11.01 V (2.29%)469.0 V18.17 V (3.78%)12399.8 WDrop/Amp High
2 AWG33.62 mm²115 A8.74 V (1.82%)471.3 V14.41 V (3.0%)9836.5 WDrop/Amp High
1 AWG42.41 mm²130 A6.93 V (1.44%)473.1 V11.42 V (2.38%)7797.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.49 V (1.14%)474.5 V9.06 V (1.89%)6182.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.36 V (0.91%)475.6 V7.19 V (1.5%)4904.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.46 V (0.72%)476.5 V5.7 V (1.19%)3890.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.74 V (0.57%)477.3 V4.52 V (0.94%)3084.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.32 V (0.48%)477.7 V3.82 V (0.8%)2610.1 WDrop/Amp High
300 kcmil152.0 mm²285 A1.93 V (0.4%)478.1 V3.19 V (0.66%)2175.7 WDrop/Amp High
350 kcmil177.3 mm²310 A1.66 V (0.35%)478.3 V2.73 V (0.57%)1865.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.45 V (0.3%)478.6 V2.39 V (0.5%)1631.5 WDrop/Amp High
500 kcmil253.4 mm²380 A1.16 V (0.24%)478.8 V1.91 V (0.4%)1305.1 WDrop/Amp High
600 kcmil304.0 mm²420 A0.97 V (0.2%)479.0 V1.59 V (0.33%)1087.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.77 V (0.16%)479.2 V1.28 V (0.27%)870.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.58 V (0.12%)479.4 V0.96 V (0.2%)652.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 40 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 40 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.29V (0.06%) and delivers 479.7V at the load.

What size aluminum wire is required for 650 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.96V (0.2%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.