🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 350 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.22%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.37V (4.02%)
Voltage at Load End205.5 VLoss: 2.54 V (2855.4 W)
Power & Breaker (125%)234.17 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 350 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1235.68 V (594.08%)0.0 V2038.3 V (979.95%)1391173.9 WDrop/Amp High
12 AWG3.31 mm²20 A776.5 V (373.32%)0.0 V1280.87 V (615.8%)874212.0 WDrop/Amp High
10 AWG5.26 mm²30 A488.64 V (234.92%)0.0 V806.02 V (387.51%)550122.0 WDrop/Amp High
8 AWG8.37 mm²50 A307.08 V (147.63%)0.0 V506.53 V (243.52%)345715.8 WDrop/Amp High
6 AWG13.3 mm²65 A193.25 V (92.91%)14.8 V318.77 V (153.26%)217567.0 WDrop/Amp High
4 AWG21.15 mm²85 A121.52 V (58.42%)86.5 V200.46 V (96.37%)136815.2 WDrop/Amp High
3 AWG26.67 mm²100 A96.37 V (46.33%)111.6 V158.97 V (76.43%)108498.0 WDrop/Amp High
2 AWG33.62 mm²115 A76.45 V (36.75%)131.6 V126.11 V (60.63%)86069.1 WDrop/Amp High
1 AWG42.41 mm²130 A60.6 V (29.14%)147.4 V99.97 V (48.06%)68230.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A48.05 V (23.1%)159.9 V79.26 V (38.11%)54096.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A38.12 V (18.33%)169.9 V62.88 V (30.23%)42913.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A30.23 V (14.54%)177.8 V49.87 V (23.98%)34038.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.98 V (11.53%)184.0 V39.55 V (19.01%)26992.9 WDrop/Amp High
250 kcmil126.7 mm²255 A20.29 V (9.75%)187.7 V33.46 V (16.09%)22838.5 WDrop/Amp High
300 kcmil152.0 mm²285 A16.91 V (8.13%)191.1 V27.89 V (13.41%)19037.1 WDrop/Amp High
350 kcmil177.3 mm²310 A14.5 V (6.97%)193.5 V23.91 V (11.5%)16320.6 WDrop/Amp High
400 kcmil202.7 mm²335 A12.68 V (6.1%)195.3 V20.92 V (10.06%)14275.5 WDrop/Amp High
500 kcmil253.4 mm²380 A10.14 V (4.88%)197.9 V16.73 V (8.04%)11419.3 WDrop/Amp High
600 kcmil304.0 mm²420 A8.45 V (4.06%)199.5 V13.95 V (6.7%)9518.6 WDrop/Amp High
750 kcmil380.0 mm²475 A6.76 V (3.25%)201.2 V11.16 V (5.36%)7614.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.07 V (2.44%)202.9 V8.37 V (4.02%)5710.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 350 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 350 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.54V (1.22%) and delivers 205.5V at the load.

What size aluminum wire is required for 650 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.37V (4.02%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.