🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 16.56V (13.8%)
Voltage at Load End116.7 VLoss: 3.35 V (2175.5 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2446.02 V (2038.35%)0.0 V4034.79 V (3362.32%)1589913.0 WDrop/Amp High
12 AWG3.31 mm²20 A1537.08 V (1280.9%)0.0 V2535.46 V (2112.88%)999099.4 WDrop/Amp High
10 AWG5.26 mm²30 A967.25 V (806.04%)0.0 V1595.51 V (1329.59%)628710.8 WDrop/Amp High
8 AWG8.37 mm²50 A607.85 V (506.54%)0.0 V1002.67 V (835.56%)395103.8 WDrop/Amp High
6 AWG13.3 mm²65 A382.54 V (318.78%)0.0 V631.0 V (525.84%)248648.0 WDrop/Amp High
4 AWG21.15 mm²85 A240.55 V (200.46%)0.0 V396.8 V (330.67%)156360.2 WDrop/Amp High
3 AWG26.67 mm²100 A190.77 V (158.97%)0.0 V314.67 V (262.23%)123997.7 WDrop/Amp High
2 AWG33.62 mm²115 A151.33 V (126.11%)0.0 V249.62 V (208.02%)98364.6 WDrop/Amp High
1 AWG42.41 mm²130 A119.97 V (99.97%)0.0 V197.89 V (164.91%)77977.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A95.12 V (79.26%)24.9 V156.9 V (130.75%)61825.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A75.45 V (62.88%)44.5 V124.46 V (103.72%)49043.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A59.85 V (49.87%)60.2 V98.72 V (82.27%)38901.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A47.46 V (39.55%)72.5 V78.29 V (65.24%)30849.1 WDrop/Amp High
250 kcmil126.7 mm²255 A40.16 V (33.46%)79.8 V66.24 V (55.2%)26101.2 WDrop/Amp High
300 kcmil152.0 mm²285 A33.47 V (27.89%)86.5 V55.21 V (46.01%)21756.7 WDrop/Amp High
350 kcmil177.3 mm²310 A28.7 V (23.91%)91.3 V47.33 V (39.45%)18652.1 WDrop/Amp High
400 kcmil202.7 mm²335 A25.1 V (20.92%)94.9 V41.4 V (34.5%)16314.8 WDrop/Amp High
500 kcmil253.4 mm²380 A20.08 V (16.73%)99.9 V33.12 V (27.6%)13050.6 WDrop/Amp High
600 kcmil304.0 mm²420 A16.74 V (13.95%)103.3 V27.61 V (23.01%)10878.4 WDrop/Amp High
750 kcmil380.0 mm²475 A13.39 V (11.16%)106.6 V22.09 V (18.4%)8702.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.04 V (8.37%)110.0 V16.56 V (13.8%)6526.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 600 feet one-way at 120V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.35V (2.79%) and delivers 116.7V at the load.

What size aluminum wire is required for 650 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 16.56V (13.8%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.