⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.08V (9.2%)
Voltage at Load End233.3 VLoss: 6.7 V (4351.1 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3261.36 V (1358.9%)0.0 V5379.72 V (2241.55%)2119884.0 WDrop/Amp High
12 AWG3.31 mm²20 A2049.43 V (853.93%)0.0 V3380.61 V (1408.59%)1332132.5 WDrop/Amp High
10 AWG5.26 mm²30 A1289.66 V (537.36%)0.0 V2127.34 V (886.39%)838281.1 WDrop/Amp High
8 AWG8.37 mm²50 A810.47 V (337.7%)0.0 V1336.9 V (557.04%)526805.1 WDrop/Amp High
6 AWG13.3 mm²65 A510.05 V (212.52%)0.0 V841.34 V (350.56%)331530.7 WDrop/Amp High
4 AWG21.15 mm²85 A320.74 V (133.64%)0.0 V529.07 V (220.45%)208480.3 WDrop/Amp High
3 AWG26.67 mm²100 A254.35 V (105.98%)0.0 V419.57 V (174.82%)165330.3 WDrop/Amp High
2 AWG33.62 mm²115 A201.77 V (84.07%)38.2 V332.83 V (138.68%)131152.8 WDrop/Amp High
1 AWG42.41 mm²130 A159.95 V (66.65%)80.0 V263.85 V (109.94%)103969.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A126.82 V (52.84%)113.2 V209.19 V (87.16%)82433.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A100.6 V (41.92%)139.4 V165.95 V (69.14%)65391.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A79.8 V (33.25%)160.2 V131.63 V (54.85%)51868.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A63.28 V (26.37%)176.7 V104.38 V (43.49%)41132.1 WDrop/Amp High
250 kcmil126.7 mm²255 A53.54 V (22.31%)186.5 V88.32 V (36.8%)34801.6 WDrop/Amp High
300 kcmil152.0 mm²285 A44.63 V (18.6%)195.4 V73.62 V (30.67%)29008.9 WDrop/Amp High
350 kcmil177.3 mm²310 A38.26 V (15.94%)201.7 V63.11 V (26.3%)24869.5 WDrop/Amp High
400 kcmil202.7 mm²335 A33.47 V (13.94%)206.5 V55.2 V (23.0%)21753.1 WDrop/Amp High
500 kcmil253.4 mm²380 A26.77 V (11.15%)213.2 V44.16 V (18.4%)17400.8 WDrop/Amp High
600 kcmil304.0 mm²420 A22.31 V (9.3%)217.7 V36.81 V (15.34%)14504.5 WDrop/Amp High
750 kcmil380.0 mm²475 A17.85 V (7.44%)222.1 V29.45 V (12.27%)11603.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.39 V (5.58%)226.6 V22.08 V (9.2%)8702.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 800 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.7V (2.79%) and delivers 233.3V at the load.

What size aluminum wire is required for 650 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.08V (9.2%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.