⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 800 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.42%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.13V (7.97%)
Voltage at Load End234.2 VLoss: 5.79 V (6526.6 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2824.42 V (1176.84%)0.0 V4658.97 V (1941.24%)3179826.0 WDrop/Amp High
12 AWG3.31 mm²20 A1774.86 V (739.53%)0.0 V2927.69 V (1219.87%)1998198.8 WDrop/Amp High
10 AWG5.26 mm²30 A1116.88 V (465.37%)0.0 V1842.33 V (767.64%)1257421.7 WDrop/Amp High
8 AWG8.37 mm²50 A701.89 V (292.45%)0.0 V1157.79 V (482.41%)790207.7 WDrop/Amp High
6 AWG13.3 mm²65 A441.71 V (184.05%)0.0 V728.62 V (303.59%)497296.1 WDrop/Amp High
4 AWG21.15 mm²85 A277.77 V (115.74%)0.0 V458.19 V (190.91%)312720.5 WDrop/Amp High
3 AWG26.67 mm²100 A220.28 V (91.78%)19.7 V363.35 V (151.4%)247995.4 WDrop/Amp High
2 AWG33.62 mm²115 A174.74 V (72.81%)65.3 V288.24 V (120.1%)196729.3 WDrop/Amp High
1 AWG42.41 mm²130 A138.52 V (57.72%)101.5 V228.5 V (95.21%)155954.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A109.83 V (45.76%)130.2 V181.17 V (75.49%)123650.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A87.12 V (36.3%)152.9 V143.71 V (59.88%)98087.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A69.11 V (28.79%)170.9 V113.99 V (47.5%)77803.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A54.8 V (22.83%)185.2 V90.4 V (37.67%)61698.1 WDrop/Amp High
250 kcmil126.7 mm²255 A46.37 V (19.32%)193.6 V76.49 V (31.87%)52202.4 WDrop/Amp High
300 kcmil152.0 mm²285 A38.65 V (16.1%)201.4 V63.75 V (26.56%)43513.4 WDrop/Amp High
350 kcmil177.3 mm²310 A33.13 V (13.81%)206.9 V54.66 V (22.77%)37304.2 WDrop/Amp High
400 kcmil202.7 mm²335 A28.98 V (12.08%)211.0 V47.81 V (19.92%)32629.7 WDrop/Amp High
500 kcmil253.4 mm²380 A23.18 V (9.66%)216.8 V38.24 V (15.93%)26101.2 WDrop/Amp High
600 kcmil304.0 mm²420 A19.32 V (8.05%)220.7 V31.88 V (13.28%)21756.7 WDrop/Amp High
750 kcmil380.0 mm²475 A15.46 V (6.44%)224.5 V25.5 V (10.63%)17405.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.59 V (4.83%)228.4 V19.13 V (7.97%)13053.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 800 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.79V (2.42%) and delivers 234.2V at the load.

What size aluminum wire is required for 650 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.13V (7.97%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.