⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.54%
Aluminum Wire (≤3% Drop)3 AWGDrop: 1.69V (0.71%)
Voltage at Load End238.7 VLoss: 1.3 V (90.7 W)
Power & Breaker (125%)16.8 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A13.17 V (5.49%)226.8 V21.73 V (9.05%)922.0 WDrop/Amp High
12 AWG3.31 mm²20 A8.28 V (3.45%)231.7 V13.65 V (5.69%)579.4 WDrop/Amp High
10 AWG5.26 mm²30 A5.21 V (2.17%)234.8 V8.59 V (3.58%)364.6 WDrop/Amp High
8 AWG8.37 mm²50 A3.27 V (1.36%)236.7 V5.4 V (2.25%)229.1 WDrop/Amp High
6 AWG13.3 mm²65 A2.06 V (0.86%)237.9 V3.4 V (1.42%)144.2 WDrop/Amp High
4 AWG21.15 mm²85 A1.3 V (0.54%)238.7 V2.14 V (0.89%)90.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.03 V (0.43%)239.0 V1.69 V (0.71%)71.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.81 V (0.34%)239.2 V1.34 V (0.56%)57.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.65 V (0.27%)239.4 V1.07 V (0.44%)45.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.51 V (0.21%)239.5 V0.84 V (0.35%)35.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.41 V (0.17%)239.6 V0.67 V (0.28%)28.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.32 V (0.13%)239.7 V0.53 V (0.22%)22.6 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.26 V (0.11%)239.7 V0.42 V (0.18%)17.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.22 V (0.09%)239.8 V0.36 V (0.15%)15.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.18 V (0.08%)239.8 V0.3 V (0.12%)12.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.15 V (0.06%)239.8 V0.25 V (0.11%)10.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.14 V (0.06%)239.9 V0.22 V (0.09%)9.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.11 V (0.05%)239.9 V0.18 V (0.07%)7.6 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.04%)239.9 V0.15 V (0.06%)6.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.03%)239.9 V0.12 V (0.05%)5.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)239.9 V0.09 V (0.04%)3.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 30 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.3V (0.54%) and delivers 238.7V at the load.

What size aluminum wire is required for 70 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 1.69V (0.71%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.