⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)3 AWGDrop: 7.06V (2.94%)
Voltage at Load End234.6 VLoss: 5.4 V (377.8 W)
Power & Breaker (125%)16.8 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A54.88 V (22.87%)185.1 V90.52 V (37.72%)3841.5 WDrop/Amp High
12 AWG3.31 mm²20 A34.49 V (14.37%)205.5 V56.89 V (23.7%)2414.0 WDrop/Amp High
10 AWG5.26 mm²30 A21.7 V (9.04%)218.3 V35.8 V (14.92%)1519.1 WDrop/Amp High
8 AWG8.37 mm²50 A13.64 V (5.68%)226.4 V22.5 V (9.37%)954.6 WDrop/Amp High
6 AWG13.3 mm²65 A8.58 V (3.58%)231.4 V14.16 V (5.9%)600.8 WDrop/Amp High
4 AWG21.15 mm²85 A5.4 V (2.25%)234.6 V8.9 V (3.71%)377.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A4.28 V (1.78%)235.7 V7.06 V (2.94%)299.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A3.4 V (1.41%)236.6 V5.6 V (2.33%)237.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A2.69 V (1.12%)237.3 V4.44 V (1.85%)188.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.13 V (0.89%)237.9 V3.52 V (1.47%)149.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A1.69 V (0.71%)238.3 V2.79 V (1.16%)118.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.34 V (0.56%)238.7 V2.21 V (0.92%)94.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.06 V (0.44%)238.9 V1.76 V (0.73%)74.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.9 V (0.38%)239.1 V1.49 V (0.62%)63.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.75 V (0.31%)239.2 V1.24 V (0.52%)52.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.64 V (0.27%)239.4 V1.06 V (0.44%)45.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.56 V (0.23%)239.4 V0.93 V (0.39%)39.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.45 V (0.19%)239.5 V0.74 V (0.31%)31.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.38 V (0.16%)239.6 V0.62 V (0.26%)26.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.3 V (0.13%)239.7 V0.5 V (0.21%)21.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.23 V (0.09%)239.8 V0.37 V (0.15%)15.8 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 125 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 5.4V (2.25%) and delivers 234.6V at the load.

What size aluminum wire is required for 70 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 7.06V (2.94%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.