🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 400 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.47%
Aluminum Wire (≤3% Drop)1 AWGDrop: 12.3V (2.56%)
Voltage at Load End468.1 VLoss: 11.86 V (1438.1 W)
Power & Breaker (125%)58.2 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 400 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.08 V (31.68%)327.9 V250.87 V (52.26%)18439.2 WDrop/Amp High
12 AWG3.31 mm²20 A95.57 V (19.91%)384.4 V157.65 V (32.84%)11587.2 WDrop/Amp High
10 AWG5.26 mm²30 A60.14 V (12.53%)419.9 V99.2 V (20.67%)7291.6 WDrop/Amp High
8 AWG8.37 mm²50 A37.79 V (7.87%)442.2 V62.34 V (12.99%)4582.3 WDrop/Amp High
6 AWG13.3 mm²65 A23.78 V (4.96%)456.2 V39.23 V (8.17%)2883.7 WDrop/Amp High
4 AWG21.15 mm²85 A14.96 V (3.12%)465.0 V24.67 V (5.14%)1813.4 W~ ≤5%
3 AWG26.67 mm²100 A11.86 V (2.47%)468.1 V19.57 V (4.08%)1438.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A9.41 V (1.96%)470.6 V15.52 V (3.23%)1140.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A7.46 V (1.55%)472.5 V12.3 V (2.56%)904.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A5.91 V (1.23%)474.1 V9.76 V (2.03%)717.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.69 V (0.98%)475.3 V7.74 V (1.61%)568.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.72 V (0.78%)476.3 V6.14 V (1.28%)451.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.95 V (0.61%)477.0 V4.87 V (1.01%)357.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.5 V (0.52%)477.5 V4.12 V (0.86%)302.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.08 V (0.43%)477.9 V3.43 V (0.72%)252.3 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.78 V (0.37%)478.2 V2.94 V (0.61%)216.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.56 V (0.33%)478.4 V2.57 V (0.54%)189.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.25 V (0.26%)478.8 V2.06 V (0.43%)151.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.04 V (0.22%)479.0 V1.72 V (0.36%)126.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.83 V (0.17%)479.2 V1.37 V (0.29%)100.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.62 V (0.13%)479.4 V1.03 V (0.21%)75.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 400 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 400 feet one-way at 480V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 11.86V (2.47%) and delivers 468.1V at the load.

What size aluminum wire is required for 70 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 12.3V (2.56%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.