🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 0.23%
Aluminum Wire (≤3% Drop)3 AWGDrop: 1.47V (0.31%)
Voltage at Load End478.9 VLoss: 1.12 V (136.0 W)
Power & Breaker (125%)58.2 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A11.41 V (2.38%)468.6 V18.82 V (3.92%)1382.9 WDrop/Amp High
12 AWG3.31 mm²20 A7.17 V (1.49%)472.8 V11.82 V (2.46%)869.0 WDrop/Amp High
10 AWG5.26 mm²30 A4.51 V (0.94%)475.5 V7.44 V (1.55%)546.9 WDrop/Amp High
8 AWG8.37 mm²50 A2.83 V (0.59%)477.2 V4.68 V (0.97%)343.7 WDrop/Amp High
6 AWG13.3 mm²65 A1.78 V (0.37%)478.2 V2.94 V (0.61%)216.3 WDrop/Amp High
4 AWG21.15 mm²85 A1.12 V (0.23%)478.9 V1.85 V (0.39%)136.0 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.89 V (0.19%)479.1 V1.47 V (0.31%)107.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.71 V (0.15%)479.3 V1.16 V (0.24%)85.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.56 V (0.12%)479.4 V0.92 V (0.19%)67.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.44 V (0.09%)479.6 V0.73 V (0.15%)53.8 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.35 V (0.07%)479.6 V0.58 V (0.12%)42.7 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.28 V (0.06%)479.7 V0.46 V (0.1%)33.8 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.22 V (0.05%)479.8 V0.37 V (0.08%)26.8 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.19 V (0.04%)479.8 V0.31 V (0.06%)22.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.16 V (0.03%)479.8 V0.26 V (0.05%)18.9 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.13 V (0.03%)479.9 V0.22 V (0.05%)16.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.12 V (0.02%)479.9 V0.19 V (0.04%)14.2 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.09 V (0.02%)479.9 V0.15 V (0.03%)11.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.08 V (0.02%)479.9 V0.13 V (0.03%)9.5 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.06 V (0.01%)479.9 V0.1 V (0.02%)7.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.01%)480.0 V0.08 V (0.02%)5.7 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 30 feet one-way at 480V (3-Phase), you need 4 AWG copper wire. This produces a voltage drop of 1.12V (0.23%) and delivers 478.9V at the load.

What size aluminum wire is required for 70 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 1.47V (0.31%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.