⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 200 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.65%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 5.15V (2.15%)
Voltage at Load End238.4 VLoss: 1.56 V (1892.3 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 200 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A760.42 V (316.84%)0.0 V1254.34 V (522.64%)921961.4 WDrop/Amp High
12 AWG3.31 mm²20 A477.85 V (199.1%)0.0 V788.23 V (328.43%)579359.4 WDrop/Amp High
10 AWG5.26 mm²30 A300.7 V (125.29%)0.0 V496.01 V (206.67%)364577.9 WDrop/Amp High
8 AWG8.37 mm²50 A188.97 V (78.74%)51.0 V311.71 V (129.88%)229113.5 WDrop/Amp High
6 AWG13.3 mm²65 A118.92 V (49.55%)121.1 V196.17 V (81.74%)144186.4 WDrop/Amp High
4 AWG21.15 mm²85 A74.78 V (31.16%)165.2 V123.36 V (51.4%)90670.4 WDrop/Amp High
3 AWG26.67 mm²100 A59.31 V (24.71%)180.7 V97.83 V (40.76%)71904.0 WDrop/Amp High
2 AWG33.62 mm²115 A47.05 V (19.6%)193.0 V77.6 V (32.33%)57039.8 WDrop/Amp High
1 AWG42.41 mm²130 A37.29 V (15.54%)202.7 V61.52 V (25.63%)45217.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A29.57 V (12.32%)210.4 V48.78 V (20.32%)35851.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A23.46 V (9.77%)216.5 V38.69 V (16.12%)28439.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A18.61 V (7.75%)221.4 V30.69 V (12.79%)22558.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A14.75 V (6.15%)225.2 V24.34 V (10.14%)17888.8 WDrop/Amp High
250 kcmil126.7 mm²255 A12.48 V (5.2%)227.5 V20.59 V (8.58%)15135.6 WDrop/Amp High
300 kcmil152.0 mm²285 A10.41 V (4.34%)229.6 V17.16 V (7.15%)12616.3 WDrop/Amp High
350 kcmil177.3 mm²310 A8.92 V (3.72%)231.1 V14.72 V (6.13%)10816.0 WDrop/Amp High
400 kcmil202.7 mm²335 A7.8 V (3.25%)232.2 V12.87 V (5.36%)9460.7 WDrop/Amp High
500 kcmil253.4 mm²380 A6.24 V (2.6%)233.8 V10.3 V (4.29%)7567.8 WDrop/Amp High
600 kcmil304.0 mm²420 A5.2 V (2.17%)234.8 V8.58 V (3.58%)6308.2 WDrop/Amp High
750 kcmil380.0 mm²475 A4.16 V (1.73%)235.8 V6.87 V (2.86%)5046.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A3.12 V (1.3%)236.9 V5.15 V (2.15%)3784.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 200 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 200 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.56V (0.65%) and delivers 238.4V at the load.

What size aluminum wire is required for 700 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 5.15V (2.15%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.