🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 450 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.69%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.38V (5.57%)
Voltage at Load End235.9 VLoss: 4.05 V (2838.5 W)
Power & Breaker (125%)168.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1975.63 V (823.18%)0.0 V3258.87 V (1357.86%)1382942.1 WDrop/Amp High
12 AWG3.31 mm²20 A1241.48 V (517.29%)0.0 V2047.87 V (853.28%)869039.1 WDrop/Amp High
10 AWG5.26 mm²30 A781.24 V (325.52%)0.0 V1288.68 V (536.95%)546866.8 WDrop/Amp High
8 AWG8.37 mm²50 A490.96 V (204.57%)0.0 V809.85 V (337.44%)343670.2 WDrop/Amp High
6 AWG13.3 mm²65 A308.97 V (128.74%)0.0 V509.66 V (212.36%)216279.7 WDrop/Amp High
4 AWG21.15 mm²85 A194.29 V (80.96%)45.7 V320.49 V (133.54%)136005.7 WDrop/Amp High
3 AWG26.67 mm²100 A154.08 V (64.2%)85.9 V254.16 V (105.9%)107856.0 WDrop/Amp High
2 AWG33.62 mm²115 A122.23 V (50.93%)117.8 V201.62 V (84.01%)85559.8 WDrop/Amp High
1 AWG42.41 mm²130 A96.89 V (40.37%)143.1 V159.83 V (66.6%)67826.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A76.82 V (32.01%)163.2 V126.72 V (52.8%)53776.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A60.94 V (25.39%)179.1 V100.53 V (41.89%)42659.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A48.34 V (20.14%)191.7 V79.74 V (33.22%)33837.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A38.33 V (15.97%)201.7 V63.23 V (26.35%)26833.2 WDrop/Amp High
250 kcmil126.7 mm²255 A32.43 V (13.51%)207.6 V53.5 V (22.29%)22703.4 WDrop/Amp High
300 kcmil152.0 mm²285 A27.03 V (11.26%)213.0 V44.6 V (18.58%)18924.5 WDrop/Amp High
350 kcmil177.3 mm²310 A23.18 V (9.66%)216.8 V38.23 V (15.93%)16224.0 WDrop/Amp High
400 kcmil202.7 mm²335 A20.27 V (8.45%)219.7 V33.44 V (13.93%)14191.0 WDrop/Amp High
500 kcmil253.4 mm²380 A16.22 V (6.76%)223.8 V26.75 V (11.15%)11351.7 WDrop/Amp High
600 kcmil304.0 mm²420 A13.52 V (5.63%)226.5 V22.3 V (9.29%)9462.2 WDrop/Amp High
750 kcmil380.0 mm²475 A10.81 V (4.51%)229.2 V17.84 V (7.43%)7569.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.11 V (3.38%)231.9 V13.38 V (5.57%)5677.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 450 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.05V (1.69%) and delivers 235.9V at the load.

What size aluminum wire is required for 700 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.38V (5.57%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.