🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 600 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.25%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.84V (14.86%)
Voltage at Load End117.3 VLoss: 2.7 V (1892.3 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 600 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2634.18 V (2195.15%)0.0 V4345.16 V (3620.97%)1843922.8 WDrop/Amp High
12 AWG3.31 mm²20 A1655.31 V (1379.43%)0.0 V2730.49 V (2275.41%)1158718.8 WDrop/Amp High
10 AWG5.26 mm²30 A1041.65 V (868.04%)0.0 V1718.24 V (1431.86%)729155.8 WDrop/Amp High
8 AWG8.37 mm²50 A654.61 V (545.51%)0.0 V1079.8 V (899.83%)458226.9 WDrop/Amp High
6 AWG13.3 mm²65 A411.96 V (343.3%)0.0 V679.54 V (566.29%)288372.9 WDrop/Amp High
4 AWG21.15 mm²85 A259.06 V (215.88%)0.0 V427.33 V (356.1%)181340.9 WDrop/Amp High
3 AWG26.67 mm²100 A205.44 V (171.2%)0.0 V338.88 V (282.4%)143808.0 WDrop/Amp High
2 AWG33.62 mm²115 A162.97 V (135.81%)0.0 V268.83 V (224.02%)114079.7 WDrop/Amp High
1 AWG42.41 mm²130 A129.19 V (107.66%)0.0 V213.11 V (177.59%)90435.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A102.43 V (85.36%)17.6 V168.96 V (140.8%)71702.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A81.26 V (67.71%)38.7 V134.03 V (111.7%)56879.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A64.45 V (53.71%)55.5 V106.32 V (88.6%)45116.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A51.11 V (42.59%)68.9 V84.31 V (70.26%)35777.6 WDrop/Amp High
250 kcmil126.7 mm²255 A43.24 V (36.04%)76.8 V71.33 V (59.44%)30271.2 WDrop/Amp High
300 kcmil152.0 mm²285 A36.05 V (30.04%)84.0 V59.46 V (49.55%)25232.6 WDrop/Amp High
350 kcmil177.3 mm²310 A30.9 V (25.75%)89.1 V50.98 V (42.48%)21632.0 WDrop/Amp High
400 kcmil202.7 mm²335 A27.03 V (22.53%)93.0 V44.59 V (37.16%)18921.4 WDrop/Amp High
500 kcmil253.4 mm²380 A21.62 V (18.02%)98.4 V35.67 V (29.72%)15135.6 WDrop/Amp High
600 kcmil304.0 mm²420 A18.02 V (15.02%)102.0 V29.73 V (24.78%)12616.3 WDrop/Amp High
750 kcmil380.0 mm²475 A14.42 V (12.02%)105.6 V23.78 V (19.82%)10093.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.81 V (9.01%)109.2 V17.84 V (14.86%)7569.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 600 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 600 feet one-way at 120V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.7V (2.25%) and delivers 117.3V at the load.

What size aluminum wire is required for 700 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.84V (14.86%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.