🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.45V (6.44%)
Voltage at Load End235.3 VLoss: 4.68 V (5676.9 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2281.26 V (950.53%)0.0 V3763.02 V (1567.92%)2765884.2 WDrop/Amp High
12 AWG3.31 mm²20 A1433.54 V (597.31%)0.0 V2364.68 V (985.28%)1738078.3 WDrop/Amp High
10 AWG5.26 mm²30 A902.1 V (375.87%)0.0 V1488.04 V (620.02%)1093733.7 WDrop/Amp High
8 AWG8.37 mm²50 A566.91 V (236.21%)0.0 V935.13 V (389.64%)687340.4 WDrop/Amp High
6 AWG13.3 mm²65 A356.77 V (148.65%)0.0 V588.5 V (245.21%)432559.3 WDrop/Amp High
4 AWG21.15 mm²85 A224.35 V (93.48%)15.6 V370.07 V (154.2%)272011.3 WDrop/Amp High
3 AWG26.67 mm²100 A177.92 V (74.13%)62.1 V293.48 V (122.28%)215712.0 WDrop/Amp High
2 AWG33.62 mm²115 A141.14 V (58.81%)98.9 V232.81 V (97.0%)171119.5 WDrop/Amp High
1 AWG42.41 mm²130 A111.88 V (46.62%)128.1 V184.56 V (76.9%)135652.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A88.71 V (36.96%)151.3 V146.33 V (60.97%)107553.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A70.37 V (29.32%)169.6 V116.08 V (48.37%)85318.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A55.82 V (23.26%)184.2 V92.07 V (38.36%)67674.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A44.26 V (18.44%)195.7 V73.01 V (30.42%)53666.4 WDrop/Amp High
250 kcmil126.7 mm²255 A37.45 V (15.6%)202.5 V61.78 V (25.74%)45406.8 WDrop/Amp High
300 kcmil152.0 mm²285 A31.22 V (13.01%)208.8 V51.49 V (21.46%)37848.9 WDrop/Amp High
350 kcmil177.3 mm²310 A26.76 V (11.15%)213.2 V44.15 V (18.39%)32448.0 WDrop/Amp High
400 kcmil202.7 mm²335 A23.41 V (9.75%)216.6 V38.61 V (16.09%)28382.0 WDrop/Amp High
500 kcmil253.4 mm²380 A18.73 V (7.8%)221.3 V30.89 V (12.87%)22703.4 WDrop/Amp High
600 kcmil304.0 mm²420 A15.61 V (6.5%)224.4 V25.75 V (10.73%)18924.5 WDrop/Amp High
750 kcmil380.0 mm²475 A12.49 V (5.2%)227.5 V20.6 V (8.58%)15139.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.36 V (3.9%)230.6 V15.45 V (6.44%)11353.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 600 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.68V (1.95%) and delivers 235.3V at the load.

What size aluminum wire is required for 700 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.45V (6.44%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.