⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 750 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.44%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 19.31V (8.05%)
Voltage at Load End234.1 VLoss: 5.86 V (7096.2 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2851.58 V (1188.16%)0.0 V4703.77 V (1959.91%)3457355.2 WDrop/Amp High
12 AWG3.31 mm²20 A1791.93 V (746.64%)0.0 V2955.84 V (1231.6%)2172597.8 WDrop/Amp High
10 AWG5.26 mm²30 A1127.62 V (469.84%)0.0 V1860.05 V (775.02%)1367167.1 WDrop/Amp High
8 AWG8.37 mm²50 A708.64 V (295.26%)0.0 V1168.92 V (487.05%)859175.5 WDrop/Amp High
6 AWG13.3 mm²65 A445.96 V (185.82%)0.0 V735.63 V (306.51%)540699.2 WDrop/Amp High
4 AWG21.15 mm²85 A280.44 V (116.85%)0.0 V462.59 V (192.75%)340014.1 WDrop/Amp High
3 AWG26.67 mm²100 A222.4 V (92.66%)17.6 V366.85 V (152.85%)269640.0 WDrop/Amp High
2 AWG33.62 mm²115 A176.42 V (73.51%)63.6 V291.01 V (121.26%)213899.4 WDrop/Amp High
1 AWG42.41 mm²130 A139.86 V (58.27%)100.1 V230.7 V (96.12%)169566.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A110.89 V (46.2%)129.1 V182.91 V (76.21%)134441.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A87.96 V (36.65%)152.0 V145.1 V (60.46%)106648.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A69.77 V (29.07%)170.2 V115.09 V (47.95%)84593.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A55.33 V (23.05%)184.7 V91.27 V (38.03%)67083.0 WDrop/Amp High
250 kcmil126.7 mm²255 A46.81 V (19.51%)193.2 V77.22 V (32.18%)56758.5 WDrop/Amp High
300 kcmil152.0 mm²285 A39.02 V (16.26%)201.0 V64.37 V (26.82%)47311.2 WDrop/Amp High
350 kcmil177.3 mm²310 A33.45 V (13.94%)206.5 V55.18 V (22.99%)40560.1 WDrop/Amp High
400 kcmil202.7 mm²335 A29.26 V (12.19%)210.7 V48.27 V (20.11%)35477.5 WDrop/Amp High
500 kcmil253.4 mm²380 A23.41 V (9.75%)216.6 V38.61 V (16.09%)28379.2 WDrop/Amp High
600 kcmil304.0 mm²420 A19.51 V (8.13%)220.5 V32.18 V (13.41%)23655.6 WDrop/Amp High
750 kcmil380.0 mm²475 A15.61 V (6.5%)224.4 V25.75 V (10.73%)18924.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.71 V (4.88%)228.3 V19.31 V (8.05%)14192.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 750 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.86V (2.44%) and delivers 234.1V at the load.

What size aluminum wire is required for 700 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 19.31V (8.05%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.