🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 450 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 15.29V (6.37%)
Voltage at Load End235.4 VLoss: 4.63 V (3707.4 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2257.86 V (940.78%)0.0 V3724.42 V (1551.84%)1806291.7 WDrop/Amp High
12 AWG3.31 mm²20 A1418.84 V (591.18%)0.0 V2340.42 V (975.18%)1135071.5 WDrop/Amp High
10 AWG5.26 mm²30 A892.84 V (372.02%)0.0 V1472.78 V (613.66%)714275.0 WDrop/Amp High
8 AWG8.37 mm²50 A561.09 V (233.79%)0.0 V925.54 V (385.64%)448875.4 WDrop/Amp High
6 AWG13.3 mm²65 A353.11 V (147.13%)0.0 V582.47 V (242.69%)282487.7 WDrop/Amp High
4 AWG21.15 mm²85 A222.05 V (92.52%)17.9 V366.28 V (152.62%)177640.0 WDrop/Amp High
3 AWG26.67 mm²100 A176.09 V (73.37%)63.9 V290.47 V (121.03%)140873.1 WDrop/Amp High
2 AWG33.62 mm²115 A139.69 V (58.2%)100.3 V230.42 V (96.01%)111751.5 WDrop/Amp High
1 AWG42.41 mm²130 A110.74 V (46.14%)129.3 V182.66 V (76.11%)88589.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A87.8 V (36.58%)152.2 V144.83 V (60.34%)70239.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A69.65 V (29.02%)170.4 V114.89 V (47.87%)55718.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A55.24 V (23.02%)184.8 V91.13 V (37.97%)44195.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A43.81 V (18.25%)196.2 V72.26 V (30.11%)35047.5 WDrop/Amp High
250 kcmil126.7 mm²255 A37.07 V (15.44%)202.9 V61.14 V (25.48%)29653.4 WDrop/Amp High
300 kcmil152.0 mm²285 A30.9 V (12.87%)209.1 V50.97 V (21.24%)24717.7 WDrop/Amp High
350 kcmil177.3 mm²310 A26.49 V (11.04%)213.5 V43.69 V (18.21%)21190.6 WDrop/Amp High
400 kcmil202.7 mm²335 A23.17 V (9.65%)216.8 V38.22 V (15.92%)18535.2 WDrop/Amp High
500 kcmil253.4 mm²380 A18.53 V (7.72%)221.5 V30.57 V (12.74%)14826.7 WDrop/Amp High
600 kcmil304.0 mm²420 A15.45 V (6.44%)224.6 V25.48 V (10.62%)12358.8 WDrop/Amp High
750 kcmil380.0 mm²475 A12.36 V (5.15%)227.6 V20.39 V (8.49%)9887.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A9.27 V (3.86%)230.7 V15.29 V (6.37%)7414.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 450 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.63V (1.93%) and delivers 235.4V at the load.

What size aluminum wire is required for 800 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 15.29V (6.37%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.