⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 750 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 22.07V (4.6%)
Voltage at Load End473.3 VLoss: 6.69 V (9268.5 W)
Power & Breaker (125%)665.11 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 750 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3258.95 V (678.95%)0.0 V5375.74 V (1119.95%)4515729.2 WDrop/Amp High
12 AWG3.31 mm²20 A2047.92 V (426.65%)0.0 V3378.11 V (703.77%)2837678.8 WDrop/Amp High
10 AWG5.26 mm²30 A1288.71 V (268.48%)0.0 V2125.77 V (442.87%)1785687.6 WDrop/Amp High
8 AWG8.37 mm²50 A809.87 V (168.72%)0.0 V1335.91 V (278.31%)1122188.4 WDrop/Amp High
6 AWG13.3 mm²65 A509.67 V (106.18%)0.0 V840.72 V (175.15%)706219.3 WDrop/Amp High
4 AWG21.15 mm²85 A320.5 V (66.77%)159.5 V528.68 V (110.14%)444100.1 WDrop/Amp High
3 AWG26.67 mm²100 A254.17 V (52.95%)225.8 V419.26 V (87.34%)352182.9 WDrop/Amp High
2 AWG33.62 mm²115 A201.62 V (42.01%)278.4 V332.59 V (69.29%)279378.8 WDrop/Amp High
1 AWG42.41 mm²130 A159.84 V (33.3%)320.2 V263.65 V (54.93%)221474.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A126.73 V (26.4%)353.3 V209.04 V (43.55%)175597.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A100.53 V (20.94%)379.5 V165.82 V (34.55%)139295.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A79.74 V (16.61%)400.3 V131.53 V (27.4%)110489.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A63.23 V (13.17%)416.8 V104.31 V (21.73%)87618.6 WDrop/Amp High
250 kcmil126.7 mm²255 A53.5 V (11.15%)426.5 V88.25 V (18.39%)74133.5 WDrop/Amp High
300 kcmil152.0 mm²285 A44.6 V (9.29%)435.4 V73.56 V (15.33%)61794.2 WDrop/Amp High
350 kcmil177.3 mm²310 A38.23 V (7.97%)441.8 V63.07 V (13.14%)52976.4 WDrop/Amp High
400 kcmil202.7 mm²335 A33.44 V (6.97%)446.6 V55.16 V (11.49%)46338.0 WDrop/Amp High
500 kcmil253.4 mm²380 A26.75 V (5.57%)453.2 V44.13 V (9.19%)37066.8 WDrop/Amp High
600 kcmil304.0 mm²420 A22.3 V (4.65%)457.7 V36.78 V (7.66%)30897.1 WDrop/Amp High
750 kcmil380.0 mm²475 A17.84 V (3.72%)462.2 V29.43 V (6.13%)24717.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A13.38 V (2.79%)466.6 V22.07 V (4.6%)18537.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 750 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 750 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.69V (1.4%) and delivers 473.3V at the load.

What size aluminum wire is required for 800 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 22.07V (4.6%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.