⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

800 Amp Wire Size at 800 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 800 A load over a 800 ft (243.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.29%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 27.18V (11.32%)
Voltage at Load End234.5 VLoss: 5.49 V (4394.0 W)
Power & Breaker (125%)192.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 800 Amps at 800 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4013.98 V (1672.49%)0.0 V6621.19 V (2758.83%)3211185.2 WDrop/Amp High
12 AWG3.31 mm²20 A2522.38 V (1050.99%)0.0 V4160.75 V (1733.65%)2017904.9 WDrop/Amp High
10 AWG5.26 mm²30 A1587.28 V (661.37%)0.0 V2618.27 V (1090.94%)1269822.3 WDrop/Amp High
8 AWG8.37 mm²50 A997.5 V (415.63%)0.0 V1645.41 V (685.59%)798000.6 WDrop/Amp High
6 AWG13.3 mm²65 A627.75 V (261.56%)0.0 V1035.49 V (431.46%)502200.4 WDrop/Amp High
4 AWG21.15 mm²85 A394.76 V (164.48%)0.0 V651.16 V (271.32%)315804.5 WDrop/Amp High
3 AWG26.67 mm²100 A313.05 V (130.44%)0.0 V516.39 V (215.16%)250441.1 WDrop/Amp High
2 AWG33.62 mm²115 A248.34 V (103.47%)0.0 V409.64 V (170.68%)198669.4 WDrop/Amp High
1 AWG42.41 mm²130 A196.87 V (82.03%)43.1 V324.74 V (135.31%)157492.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A156.09 V (65.04%)83.9 V257.47 V (107.28%)124869.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A123.82 V (51.59%)116.2 V204.24 V (85.1%)99054.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A98.21 V (40.92%)141.8 V162.01 V (67.5%)78570.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A77.88 V (32.45%)162.1 V128.47 V (53.53%)62306.6 WDrop/Amp High
250 kcmil126.7 mm²255 A65.9 V (27.46%)174.1 V108.7 V (45.29%)52717.2 WDrop/Amp High
300 kcmil152.0 mm²285 A54.93 V (22.89%)185.1 V90.61 V (37.75%)43942.5 WDrop/Amp High
350 kcmil177.3 mm²310 A47.09 V (19.62%)192.9 V77.68 V (32.37%)37672.1 WDrop/Amp High
400 kcmil202.7 mm²335 A41.19 V (17.16%)198.8 V67.94 V (28.31%)32951.5 WDrop/Amp High
500 kcmil253.4 mm²380 A32.95 V (13.73%)207.1 V54.35 V (22.65%)26358.6 WDrop/Amp High
600 kcmil304.0 mm²420 A27.46 V (11.44%)212.5 V45.3 V (18.88%)21971.3 WDrop/Amp High
750 kcmil380.0 mm²475 A21.97 V (9.15%)218.0 V36.24 V (15.1%)17577.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A16.48 V (6.87%)223.5 V27.18 V (11.32%)13181.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 800 amps at 800 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 800A load over 800 feet one-way at 240V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.49V (2.29%) and delivers 234.5V at the load.

What size aluminum wire is required for 800 amps at 800 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 27.18V (11.32%).

What breaker size is needed for a 800A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (800A × 1.25 = 1000.0A), which corresponds to a standard 1000A circuit breaker.