🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.1V (4.38%)
Voltage at Load End205.2 VLoss: 2.76 V (4301.1 W)
Power & Breaker (125%)324.24 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1344.32 V (646.31%)0.0 V2217.49 V (1066.1%)2095580.6 WDrop/Amp High
12 AWG3.31 mm²20 A844.77 V (406.14%)0.0 V1393.47 V (669.94%)1316860.3 WDrop/Amp High
10 AWG5.26 mm²30 A531.59 V (255.57%)0.0 V876.88 V (421.58%)828670.7 WDrop/Amp High
8 AWG8.37 mm²50 A334.07 V (160.61%)0.0 V551.06 V (264.93%)520765.5 WDrop/Amp High
6 AWG13.3 mm²65 A210.24 V (101.08%)0.0 V346.8 V (166.73%)327729.9 WDrop/Amp High
4 AWG21.15 mm²85 A132.21 V (63.56%)75.8 V218.08 V (104.85%)206090.2 WDrop/Amp High
3 AWG26.67 mm²100 A104.84 V (50.41%)103.2 V172.94 V (83.15%)163434.9 WDrop/Amp High
2 AWG33.62 mm²115 A83.17 V (39.99%)124.8 V137.19 V (65.96%)129649.2 WDrop/Amp High
1 AWG42.41 mm²130 A65.93 V (31.7%)142.1 V108.76 V (52.29%)102777.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A52.27 V (25.13%)155.7 V86.23 V (41.46%)81488.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.47 V (19.94%)166.5 V68.4 V (32.89%)64642.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A32.89 V (15.81%)175.1 V54.26 V (26.09%)51274.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.08 V (12.54%)181.9 V43.03 V (20.69%)40660.5 WDrop/Amp High
250 kcmil126.7 mm²255 A22.07 V (10.61%)185.9 V36.4 V (17.5%)34402.6 WDrop/Amp High
300 kcmil152.0 mm²285 A18.4 V (8.84%)189.6 V30.34 V (14.59%)28676.4 WDrop/Amp High
350 kcmil177.3 mm²310 A15.77 V (7.58%)192.2 V26.01 V (12.51%)24584.4 WDrop/Amp High
400 kcmil202.7 mm²335 A13.79 V (6.63%)194.2 V22.75 V (10.94%)21503.7 WDrop/Amp High
500 kcmil253.4 mm²380 A11.03 V (5.31%)197.0 V18.2 V (8.75%)17201.3 WDrop/Amp High
600 kcmil304.0 mm²420 A9.2 V (4.42%)198.8 V15.17 V (7.29%)14338.2 WDrop/Amp High
750 kcmil380.0 mm²475 A7.36 V (3.54%)200.6 V12.14 V (5.84%)11470.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.52 V (2.65%)202.5 V9.1 V (4.38%)8602.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 275 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.76V (1.32%) and delivers 205.2V at the load.

What size aluminum wire is required for 900 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.1V (4.38%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.