⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

900 Amp Wire Size at 400 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.67%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 13.24V (5.52%)
Voltage at Load End236.0 VLoss: 4.01 V (6256.2 W)
Power & Breaker (125%)374.12 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 400 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1955.37 V (814.74%)0.0 V3225.44 V (1343.93%)3048117.2 WDrop/Amp High
12 AWG3.31 mm²20 A1228.75 V (511.98%)0.0 V2026.86 V (844.53%)1915433.2 WDrop/Amp High
10 AWG5.26 mm²30 A773.23 V (322.18%)0.0 V1275.46 V (531.44%)1205339.1 WDrop/Amp High
8 AWG8.37 mm²50 A485.92 V (202.47%)0.0 V801.54 V (333.98%)757477.2 WDrop/Amp High
6 AWG13.3 mm²65 A305.8 V (127.42%)0.0 V504.43 V (210.18%)476698.0 WDrop/Amp High
4 AWG21.15 mm²85 A192.3 V (80.13%)47.7 V317.21 V (132.17%)299767.6 WDrop/Amp High
3 AWG26.67 mm²100 A152.5 V (63.54%)87.5 V251.55 V (104.81%)237723.4 WDrop/Amp High
2 AWG33.62 mm²115 A120.97 V (50.41%)119.0 V199.55 V (83.15%)188580.7 WDrop/Amp High
1 AWG42.41 mm²130 A95.9 V (39.96%)144.1 V158.19 V (65.91%)149495.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A76.04 V (31.68%)164.0 V125.42 V (52.26%)118528.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A60.32 V (25.13%)179.7 V99.49 V (41.46%)94024.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A47.84 V (19.93%)192.2 V78.92 V (32.88%)74580.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A37.94 V (15.81%)202.1 V62.58 V (26.08%)59142.6 WDrop/Amp High
250 kcmil126.7 mm²255 A32.1 V (13.38%)207.9 V52.95 V (22.06%)50040.1 WDrop/Amp High
300 kcmil152.0 mm²285 A26.76 V (11.15%)213.2 V44.14 V (18.39%)41711.1 WDrop/Amp High
350 kcmil177.3 mm²310 A22.94 V (9.56%)217.1 V37.84 V (15.77%)35759.1 WDrop/Amp High
400 kcmil202.7 mm²335 A20.06 V (8.36%)219.9 V33.1 V (13.79%)31278.2 WDrop/Amp High
500 kcmil253.4 mm²380 A16.05 V (6.69%)223.9 V26.48 V (11.03%)25020.1 WDrop/Amp High
600 kcmil304.0 mm²420 A13.38 V (5.57%)226.6 V22.07 V (9.2%)20855.5 WDrop/Amp High
750 kcmil380.0 mm²475 A10.7 V (4.46%)229.3 V17.66 V (7.36%)16684.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A8.03 V (3.34%)232.0 V13.24 V (5.52%)12512.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 400 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 400 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 4.01V (1.67%) and delivers 236.0V at the load.

What size aluminum wire is required for 900 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 13.24V (5.52%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.