900 Amp Wire Size at 450 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 900 A load over a 450 ft (137.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.17%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 17.2V (7.17%)
Voltage at Load End234.8 VLoss: 5.21 V (4692.2 W)
Power & Breaker (125%)216.0 kW1200A Breaker Recommended

All AWG & kcmil Wire Gauges for 900 Amps at 450 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2540.1 V (1058.37%)0.0 V4189.97 V (1745.82%)2286087.9 WDrop/Amp High
12 AWG3.31 mm²20 A1596.19 V (665.08%)0.0 V2632.97 V (1097.07%)1436574.9 WDrop/Amp High
10 AWG5.26 mm²30 A1004.45 V (418.52%)0.0 V1656.87 V (690.36%)904004.3 WDrop/Amp High
8 AWG8.37 mm²50 A631.23 V (263.01%)0.0 V1041.24 V (433.85%)568107.9 WDrop/Amp High
6 AWG13.3 mm²65 A397.25 V (165.52%)0.0 V655.27 V (273.03%)357523.5 WDrop/Amp High
4 AWG21.15 mm²85 A249.81 V (104.09%)0.0 V412.06 V (171.69%)224825.7 WDrop/Amp High
3 AWG26.67 mm²100 A198.1 V (82.54%)41.9 V326.78 V (136.16%)178292.6 WDrop/Amp High
2 AWG33.62 mm²115 A157.15 V (65.48%)82.8 V259.23 V (108.01%)141435.5 WDrop/Amp High
1 AWG42.41 mm²130 A124.58 V (51.91%)115.4 V205.5 V (85.62%)112121.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A98.77 V (41.16%)141.2 V162.93 V (67.89%)88896.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A78.35 V (32.65%)161.6 V129.25 V (53.85%)70518.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A62.15 V (25.9%)177.8 V102.52 V (42.72%)55935.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A49.29 V (20.54%)190.7 V81.3 V (33.87%)44356.9 WDrop/Amp High
250 kcmil126.7 mm²255 A41.7 V (17.38%)198.3 V68.79 V (28.66%)37530.1 WDrop/Amp High
300 kcmil152.0 mm²285 A34.76 V (14.48%)205.2 V57.34 V (23.89%)31283.3 WDrop/Amp High
350 kcmil177.3 mm²310 A29.8 V (12.42%)210.2 V49.15 V (20.48%)26819.3 WDrop/Amp High
400 kcmil202.7 mm²335 A26.07 V (10.86%)213.9 V43.0 V (17.91%)23458.6 WDrop/Amp High
500 kcmil253.4 mm²380 A20.85 V (8.69%)219.1 V34.39 V (14.33%)18765.0 WDrop/Amp High
600 kcmil304.0 mm²420 A17.38 V (7.24%)222.6 V28.67 V (11.95%)15641.7 WDrop/Amp High
750 kcmil380.0 mm²475 A13.9 V (5.79%)226.1 V22.93 V (9.56%)12513.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A10.43 V (4.34%)229.6 V17.2 V (7.17%)9384.4 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 900 amps at 450 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 900A load over 450 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.21V (2.17%) and delivers 234.8V at the load.

What size aluminum wire is required for 900 amps at 450 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 17.2V (7.17%).

What breaker size is needed for a 900A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (900A × 1.25 = 1125.0A), which corresponds to a standard 1200A circuit breaker.