15 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 15 A over 350 m (1148.3 ft).

Copper Cable (≤3% Drop)16 mm²Drop: 12.16V (2.93%)
Aluminum Cable (≤3% Drop)35 mm²Drop: 9.17V (2.21%)
Voltage at Load402.8 VLine Loss: 316.0 W
Max Power & Breaker10.78 kW15A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 15A at 350m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A129.73 V (31.26%)285.3 V213.99 V (51.57%)3370.5 WDrop High
2.5 mm²24 A18 A77.84 V (18.76%)337.2 V128.4 V (30.94%)2022.3 WDrop High
4 mm²32 A25 A48.65 V (11.72%)366.4 V80.25 V (19.34%)1263.9 WDrop High
6 mm²41 A32 A32.43 V (7.82%)382.6 V53.5 V (12.89%)842.6 WDrop High
10 mm²57 A44 A19.46 V (4.69%)395.5 V32.1 V (7.73%)505.6 W~ ≤5%
16 mm²76 A59 A12.16 V (2.93%)402.8 V20.06 V (4.83%)316.0 W✓ OK (≤3%)
25 mm²101 A78 A7.78 V (1.88%)407.2 V12.84 V (3.09%)202.2 W✓ OK (≤3%)
35 mm²125 A97 A5.56 V (1.34%)409.4 V9.17 V (2.21%)144.4 W✓ OK (≤3%)
50 mm²151 A118 A3.89 V (0.94%)411.1 V6.42 V (1.55%)101.1 W✓ OK (≤3%)
70 mm²192 A150 A2.78 V (0.67%)412.2 V4.59 V (1.1%)72.2 W✓ OK (≤3%)
95 mm²232 A181 A2.05 V (0.49%)413.0 V3.38 V (0.81%)53.2 W✓ OK (≤3%)
120 mm²269 A210 A1.62 V (0.39%)413.4 V2.67 V (0.64%)42.1 W✓ OK (≤3%)
150 mm²309 A241 A1.3 V (0.31%)413.7 V2.14 V (0.52%)33.7 W✓ OK (≤3%)
185 mm²353 A275 A1.05 V (0.25%)413.9 V1.74 V (0.42%)27.3 W✓ OK (≤3%)
240 mm²415 A324 A0.81 V (0.2%)414.2 V1.34 V (0.32%)21.1 W✓ OK (≤3%)
300 mm²477 A372 A0.65 V (0.16%)414.4 V1.07 V (0.26%)16.9 W✓ OK (≤3%)
400 mm²570 A445 A0.49 V (0.12%)414.5 V0.8 V (0.19%)12.6 W✓ OK (≤3%)

FAQ — 15 Amp Cable Size at 350 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 15A at 350 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 16 mm² copper cable for 15A over 350m at 415V (voltage drop: 12.16V or 2.93%).

What is the power capacity of 15A at 415V?

At unity power factor, 15A at 415V supports 10.78 kW with a standard 15A circuit breaker.