325 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 120 m (393.7 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 7.81V (1.88%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 7.95V (1.92%)
Voltage at Load407.2 VLine Loss: 4398.6 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 120m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A963.71 V (232.22%)0.0 V1589.68 V (383.05%)542490.0 WDrop High
2.5 mm²24 A18 A578.23 V (139.33%)0.0 V953.81 V (229.83%)325494.0 WDrop High
4 mm²32 A25 A361.39 V (87.08%)53.6 V596.13 V (143.65%)203433.8 WDrop High
6 mm²41 A32 A240.93 V (58.06%)174.1 V397.42 V (95.76%)135622.5 WDrop High
10 mm²57 A44 A144.56 V (34.83%)270.4 V238.45 V (57.46%)81373.5 WDrop High
16 mm²76 A59 A90.35 V (21.77%)324.7 V149.03 V (35.91%)50858.4 WDrop High
25 mm²101 A78 A57.82 V (13.93%)357.2 V95.38 V (22.98%)32549.4 WDrop High
35 mm²125 A97 A41.3 V (9.95%)373.7 V68.13 V (16.42%)23249.6 WDrop High
50 mm²151 A118 A28.91 V (6.97%)386.1 V47.69 V (11.49%)16274.7 WDrop High
70 mm²192 A150 A20.65 V (4.98%)394.3 V34.06 V (8.21%)11624.8 WDrop High
95 mm²232 A181 A15.22 V (3.67%)399.8 V25.1 V (6.05%)8565.6 WDrop High
120 mm²269 A210 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 WDrop High
150 mm²309 A241 A9.64 V (2.32%)405.4 V15.9 V (3.83%)5424.9 WDrop High
185 mm²353 A275 A7.81 V (1.88%)407.2 V12.89 V (3.11%)4398.6 W✓ OK (≤3%)
240 mm²415 A324 A6.02 V (1.45%)409.0 V9.94 V (2.39%)3390.6 W✓ OK (≤3%)
300 mm²477 A372 A4.82 V (1.16%)410.2 V7.95 V (1.92%)2712.4 W✓ OK (≤3%)
400 mm²570 A445 A3.61 V (0.87%)411.4 V5.96 V (1.44%)2034.3 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 120 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 120 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 120m at 415V (voltage drop: 7.81V or 1.88%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.