325 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 300 m (984.3 ft).

Copper Cable (≤3% Drop)300 mm²Drop: 12.05V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 14.9V (3.59%)
Voltage at Load403.0 VLine Loss: 6781.1 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 300m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A2409.28 V (580.55%)0.0 V3974.19 V (957.64%)1356225.0 WDrop High
2.5 mm²24 A18 A1445.57 V (348.33%)0.0 V2384.51 V (574.58%)813735.0 WDrop High
4 mm²32 A25 A903.48 V (217.71%)0.0 V1490.32 V (359.11%)508584.4 WDrop High
6 mm²41 A32 A602.32 V (145.14%)0.0 V993.55 V (239.41%)339056.2 WDrop High
10 mm²57 A44 A361.39 V (87.08%)53.6 V596.13 V (143.65%)203433.8 WDrop High
16 mm²76 A59 A225.87 V (54.43%)189.1 V372.58 V (89.78%)127146.1 WDrop High
25 mm²101 A78 A144.56 V (34.83%)270.4 V238.45 V (57.46%)81373.5 WDrop High
35 mm²125 A97 A103.25 V (24.88%)311.7 V170.32 V (41.04%)58123.9 WDrop High
50 mm²151 A118 A72.28 V (17.42%)342.7 V119.23 V (28.73%)40686.7 WDrop High
70 mm²192 A150 A51.63 V (12.44%)363.4 V85.16 V (20.52%)29062.0 WDrop High
95 mm²232 A181 A38.04 V (9.17%)377.0 V62.75 V (15.12%)21414.1 WDrop High
120 mm²269 A210 A30.12 V (7.26%)384.9 V49.68 V (11.97%)16952.8 WDrop High
150 mm²309 A241 A24.09 V (5.81%)390.9 V39.74 V (9.58%)13562.2 WDrop High
185 mm²353 A275 A19.53 V (4.71%)395.5 V32.22 V (7.76%)10996.4 W~ ≤5%
240 mm²415 A324 A15.06 V (3.63%)399.9 V24.84 V (5.99%)8476.4 W~ ≤5%
300 mm²477 A372 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 W✓ OK (≤3%)
400 mm²570 A445 A9.03 V (2.18%)406.0 V14.9 V (3.59%)5085.8 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 300 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 300 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 300 mm² copper cable for 325A over 300m at 415V (voltage drop: 12.05V or 2.9%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.