325 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 400 m (1312.3 ft).

Copper Cable (≤3% Drop)400 mm²Drop: 12.05V (2.9%)
Aluminum Cable (≤3% Drop)400 mm²Drop: 19.87V (4.79%)
Voltage at Load403.0 VLine Loss: 6781.1 W
Max Power & Breaker233.61 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 400m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A3212.38 V (774.07%)0.0 V5298.92 V (1276.85%)1808300.0 WDrop High
2.5 mm²24 A18 A1927.43 V (464.44%)0.0 V3179.35 V (766.11%)1084980.0 WDrop High
4 mm²32 A25 A1204.64 V (290.28%)0.0 V1987.1 V (478.82%)678112.5 WDrop High
6 mm²41 A32 A803.09 V (193.52%)0.0 V1324.73 V (319.21%)452075.0 WDrop High
10 mm²57 A44 A481.86 V (116.11%)0.0 V794.84 V (191.53%)271245.0 WDrop High
16 mm²76 A59 A301.16 V (72.57%)113.8 V496.77 V (119.7%)169528.1 WDrop High
25 mm²101 A78 A192.74 V (46.44%)222.3 V317.94 V (76.61%)108498.0 WDrop High
35 mm²125 A97 A137.67 V (33.17%)277.3 V227.1 V (54.72%)77498.6 WDrop High
50 mm²151 A118 A96.37 V (23.22%)318.6 V158.97 V (38.31%)54249.0 WDrop High
70 mm²192 A150 A68.84 V (16.59%)346.2 V113.55 V (27.36%)38749.3 WDrop High
95 mm²232 A181 A50.72 V (12.22%)364.3 V83.67 V (20.16%)28552.1 WDrop High
120 mm²269 A210 A40.15 V (9.68%)374.8 V66.24 V (15.96%)22603.7 WDrop High
150 mm²309 A241 A32.12 V (7.74%)382.9 V52.99 V (12.77%)18083.0 WDrop High
185 mm²353 A275 A26.05 V (6.28%)389.0 V42.96 V (10.35%)14661.9 WDrop High
240 mm²415 A324 A20.08 V (4.84%)394.9 V33.12 V (7.98%)11301.9 W~ ≤5%
300 mm²477 A372 A16.06 V (3.87%)398.9 V26.49 V (6.38%)9041.5 W~ ≤5%
400 mm²570 A445 A12.05 V (2.9%)403.0 V19.87 V (4.79%)6781.1 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 400 Meters (415V Three-Phase (UK / Australia Industrial))

What mm² cable size is required for 325A at 400 meters (415V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 400 mm² copper cable for 325A over 400m at 415V (voltage drop: 12.05V or 2.9%).

What is the power capacity of 325A at 415V?

At unity power factor, 325A at 415V supports 233.61 kW with a standard 350A circuit breaker.