⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
⚡ IEC 60364-5-52 · DIN VDE · NEK 400 · SS 436 40 00

325 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

IEC 60364-5-52 metric conductor sizing (mm²), voltage drop, and power loss calculation for 325 A over 80 m (262.5 ft).

Copper Cable (≤3% Drop)185 mm²Drop: 5.21V (0.75%)
Aluminum Cable (≤3% Drop)300 mm²Drop: 5.3V (0.77%)
Voltage at Load684.8 VLine Loss: 2932.4 W
Max Power & Breaker388.41 kW350A MCB/MCCB

IEC 60364 Cable Cross-Section Table (1.5 mm² – 400 mm²) for 325A at 80m

Cross-Section (mm²)Cu AmpacityAl Ampacity Cu Voltage DropLoad VoltageAl Voltage DropPower LossStatus
1.5 mm²16 A12 A642.48 V (93.11%)47.5 V1059.78 V (153.59%)361660.0 WDrop High
2.5 mm²24 A18 A385.49 V (55.87%)304.5 V635.87 V (92.16%)216996.0 WDrop High
4 mm²32 A25 A240.93 V (34.92%)449.1 V397.42 V (57.6%)135622.5 WDrop High
6 mm²41 A32 A160.62 V (23.28%)529.4 V264.95 V (38.4%)90415.0 WDrop High
10 mm²57 A44 A96.37 V (13.97%)593.6 V158.97 V (23.04%)54249.0 WDrop High
16 mm²76 A59 A60.23 V (8.73%)629.8 V99.35 V (14.4%)33905.6 WDrop High
25 mm²101 A78 A38.55 V (5.59%)651.5 V63.59 V (9.22%)21699.6 WDrop High
35 mm²125 A97 A27.53 V (3.99%)662.5 V45.42 V (6.58%)15499.7 WDrop High
50 mm²151 A118 A19.27 V (2.79%)670.7 V31.79 V (4.61%)10849.8 WDrop High
70 mm²192 A150 A13.77 V (2.0%)676.2 V22.71 V (3.29%)7749.9 WDrop High
95 mm²232 A181 A10.14 V (1.47%)679.9 V16.73 V (2.43%)5710.4 WDrop High
120 mm²269 A210 A8.03 V (1.16%)682.0 V13.25 V (1.92%)4520.8 WDrop High
150 mm²309 A241 A6.42 V (0.93%)683.6 V10.6 V (1.54%)3616.6 WDrop High
185 mm²353 A275 A5.21 V (0.75%)684.8 V8.59 V (1.25%)2932.4 W✓ OK (≤3%)
240 mm²415 A324 A4.02 V (0.58%)686.0 V6.62 V (0.96%)2260.4 W✓ OK (≤3%)
300 mm²477 A372 A3.21 V (0.47%)686.8 V5.3 V (0.77%)1808.3 W✓ OK (≤3%)
400 mm²570 A445 A2.41 V (0.35%)687.6 V3.97 V (0.58%)1356.2 W✓ OK (≤3%)

FAQ — 325 Amp Cable Size at 80 Meters (690V Three-Phase (Wind / Heavy Industrial))

What mm² cable size is required for 325A at 80 meters (690V)?

According to IEC 60364-5-52 ampacity and the 3% maximum voltage drop standard, you need 185 mm² copper cable for 325A over 80m at 690V (voltage drop: 5.21V or 0.75%).

What is the power capacity of 325A at 690V?

At unity power factor, 325A at 690V supports 388.41 kW with a standard 350A circuit breaker.